Menu
Vaša košarica

RM35BA10 Schneider Electric

RM35BA10  Schneider Electric
RM35BA10 Schneider Electric

Opis

pump control relay RM35-BA - range 1..10 A

Tehnične lastnosti

Glavno
Serija izdelkaZelio Control
Izdelek ali sestavni delmodular measurement and control relays
utilisation categoryAC-12 conforming to IEC 60947-5-1 AC-13 conforming to IEC 60947-5-1 AC-14 conforming to IEC 60947-5-1 AC-15 conforming to IEC 60947-5-1 DC-12 conforming to IEC 60947-5-1 DC-13 conforming to IEC 60947-5-1
product specific applicationfor 3-phase and single-phase pump
time delay typeadjustable 1...60 s, +/- 10 % Ti on energisation fixed 0.3 s reset on terminal Y2 adjustable 0.1...10 s, +/- 10 % Tt on crossing the threshold
measurement range1...10 A AC
switching capacity in VA1250 VA
relay nameRM35BA
relay typepump control relays
relay monitored parametersovercurrent and undercurrent control phase sequence on 3-phase supply phase failure on 3-phase supply
minimum switching current10 mA at 5 V DC
maximum switching current5 A AC/DC
maximum power consumption in VA5 VA AC
Komplementarno
mounting support35 mm symmetrical DIN rail conforming to EN/IEC 60715
Povezave - terminaliscrew terminals, 1 x 0.5...1 x 4 mm² (AWG 20...AWG 11) solid without cable end screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 12) flexible with cable end screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end
[Ui] Nazivna izolacijska trdnost400 V conforming to IEC 60664-1
electrical durability100000 cycles
mechanical durability30000000 cycles
Kompatibilnostna kodaRM3
Širina35 mm
tightening torque0.6-1 N.m conforming to IEC 60947-1
[Us] rated supply voltage208...480 V AC 3 phases 230 V AC 1 phase 208...480 V AC 3 phases 230 V AC single phase
Omejitve napajalne napetosti183-528 V AC
operating positionany position
housing materialself-extinguishing plastic
OznačevanjeCE : EMC 89/336/EEC CE : 73/23/EEC
input current11 A permanent at 25 °C E1-L2 terminals 50 A non repetitive < 1 s at 25 °C E1-L2 terminals
repeat accuracy+/- 1 % for input and measurement circuit +/- 1 % for time delay
status LED1 LED green for power ON 1 LED yellow for fault 1 LED yellow for relay ON
insulation resistance> 500 MOhm at 500 V DC between supply and relay output conforming to 60255-5 > 500 MOhm at 500 V DC between measurement and relay output conforming to 60664-1 > 1 MOhm at 500 V DC between supply and measurement conforming to 60255-5 > 500 MOhm at 500 V DC between supply and relay output conforming to 60664-1 > 500 MOhm at 500 V DC between measurement and relay output conforming to 60255-5 > 1 MOhm at 500 V DC between supply and measurement conforming to 60664-1
supply frequency50/60 Hz +/- 10 %
overvoltage categoryIII conforming to IEC 60664-1
measurement accuracy+/- 10 % of the full scale value
response time< 300 ms (in the event of a fault)
Omejitve napetosti regulacijskega vezja- 15 % + 10 % Un
resistance across terminals0.01 Ohm at E1-L2 terminals
maximum switching voltage250 V AC/DC
hysteresis5-5 % of threshold
nominal output current5 A
reset time2000 ms
operating rate<= 360 operations/hour full load
maximum measuring cycle140 ms as true rms value
measurement error1 % by volt over the whole range +/- 0.05 %/°C
output contacts1 C/O
run-up delay at power-up0.5 s
Okolje
Temperatura okoliškega zraka za delovanje-20-50 °C
IP stopnja zaščiteIP20 (terminals) conforming to IEC 60529 IP30 (casing) conforming to IEC 60529
Stopnja onesnaženosti3 conforming to IEC 60664-1
Temperatura okoliškega zraka za skladiščenje-40-70 °C
relative humidity95-95 % at 55-55 °C conforming to IEC 60068-2-30
Certifikati izdelkovC-Tick CSA GOST UL GL
StandardiEN/IEC 60255-6
Odporno proti udarcu15 gn for 11 ms conforming to IEC 60255-21-1
Odpornost proti vibracijam0.35 mm (f= 5-57.6 Hz) conforming to IEC 60068-2-6/IEC 60255-21-1 1 gn (f= 57.6-150 Hz) conforming to IEC 60068-2-6/IEC 60255-21-1
Elektromagnetna kompatibilnostemission standard for industrial environments conforming to EN/IEC 61000-6-4 emission standard for residential, commercial and light-industrial environments conforming to EN/IEC 61000-6-3 immunity for industrial environments conforming to NF EN/IEC 61000-6-2
dielectric strength2 kV AC 50 Hz (shock wave 4 kV)
immunity to microbreaks500 ms