Menu
Vaša košarica

RM35ATL0MW Schneider Electric

RM35ATL0MW  Schneider Electric
RM35ATL0MW Schneider Electric

Opis

temperature control relay RM35-A - 24..240 V AC/DC - 1 OC

Tehnične lastnosti

Glavno
Serija izdelkaZelio Control
Izdelek ali sestavni delmodular measurement and control relays
utilisation categoryAC-12 conforming to IEC 60947-5-1 AC-13 conforming to IEC 60947-5-1 AC-14 conforming to IEC 60947-5-1 AC-15 conforming to IEC 60947-5-1 DC-12 conforming to IEC 60947-5-1 DC-13 conforming to IEC 60947-5-1 DC-14 conforming to IEC 60947-5-1
product specific applicationfor elevator machine rooms and 3-phase supplies
time delay range0.1...10 s adjustable delay (tolerance: 0...10 % of the full scale value)
switching capacity in VA1250 VA
relay nameRM35AT
relay typetemperature control relays
relay monitored parametersundertemperature: -1...11°C overtemperature: 34...46°C
minimum switching current10 mA at 5 V DC
maximum power consumption in VA3.5 VA AC
Komplementarno
mounting support35 mm symmetrical DIN rail conforming to EN/IEC 60715
Povezave - terminaliscrew terminals, 1 x 0.5...1 x 4 mm² (AWG 20...AWG 11) solid without cable end screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 12) flexible with cable end screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end
[Ui] Nazivna izolacijska trdnost250 V conforming to IEC 60664-1
electrical durability100000 cycles
mechanical durability30000000 cycles
Kompatibilnostna kodaRM3
Širina35 mm
tightening torque0.6-1 N.m conforming to IEC 60947-1
[Us] rated supply voltage24...240 V AC/DC 24...240 V AC/DC
Omejitve napajalne napetosti20.4-264 V AC 21.6-264 V DC
contacts materialcadmium free
operating positionany position without
housing materialself-extinguishing plastic
OznačevanjeCE : EMC 89/336/EEC CE : 73/23/EEC
status LED1 LED green for power ON 1 LED yellow for correct temperature (high R1) 1 LED yellow for correct temperature (low R2)
insulation resistance> 500 MOhm at 500 V DC between supply and relay output conforming to IEC 60255-5 > 500 MOhm at 500 V DC between measurement and relay output conforming to IEC 60664-1 > 1 MOhm at 500 V DC between supply and measurement conforming to IEC 60255-5 > 500 MOhm at 500 V DC between supply and relay output conforming to IEC 60664-1 > 500 MOhm at 500 V DC between measurement and relay output conforming to IEC 60255-5 > 1 MOhm at 500 V DC between supply and measurement conforming to IEC 60664-1
insulationgalvanic insulation between supply and measurement
supply frequency50/60 Hz +/- 10 %
overvoltage categoryIII conforming to IEC 60664-1
measurement accuracy+/- 2 °C
response time<= 3.5 s + Tt (in case of temperature fault) <= 3.5 s (on disappearance of fault)
Omejitve napetosti regulacijskega vezja- 10 % + 10 % Un DC - 15 % + 10 % Un AC
resistance across terminals1.33 kOhm at temperature
maximum switching voltage250 V AC/DC
maximum power consumption in W0.6 W DC
nominal output current5 A
installed devicePt 100 probe cable length <= 10 m
reset time8 s
operating rate<= 360 operations/hour full load
output contacts1 C/O
run-up delay at power-up0.2 s
temperature probe typePt 100 - 3-wire
Okolje
Temperatura okoliškega zraka za delovanje-20-50 °C
IP stopnja zaščiteIP20 (terminals) conforming to IEC 60529 IP30 (casing) conforming to IEC 60529
Stopnja onesnaženosti3 conforming to IEC 60664-1
Temperatura okoliškega zraka za skladiščenje-40-70 °C
Certifikati izdelkovGOST GL C-Tick UL CSA
StandardiIEC 60255-6 NF EN 60255-6
Odporno proti udarcu15 gn for 11 ms conforming to IEC 60255-21-1
Odpornost proti vibracijam0.35 mm (f= 5-57.6 Hz) conforming to IEC 60068-2-6/IEC 60255-21-1 1 gn (f= 57.6-150 Hz) conforming to IEC 60068-2-6/IEC 60255-21-1
Elektromagnetna kompatibilnostemission standard for industrial environments conforming to EN/IEC 61000-6-4 emission standard for residential, commercial and light-industrial environments conforming to EN/IEC 61000-6-3 immunity for industrial environments conforming to NF EN/IEC 61000-6-2
non-dissipating shock wave4 kV
immunity to microbreaks10 ms
dielectric test voltage2 kV, 1 min AC 50 Hz