Menu
Vaša košarica

RM22TR31 Schneider Electric

RM22TR31  Schneider Electric
RM22TR31 Schneider Electric

Opis

three-Phase Voltage control relay 200…240Vac, 2 C/O

Tehnične lastnosti

Glavno
Serija izdelkaZelio Control
Izdelek ali sestavni delmodular measurement and control relays
network number of phases3 phases
time delay typeadjustable 0.1...30 s, +/- 10 % of the full scale value on crossing the threshold Tt
measurement range200...240 V voltage AC
switching capacity in VA2000 VA
relay nameRM22TR
relay typecontrol relay
relay monitored parametersphase sequence phase failure detection overvoltage and undervoltage detection
Komplementarno
mounting support35 mm DIN rail conforming to EN/IEC 60715
Teža izdelka0.09 kg
Povezave - terminaliscrew terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end screw terminals, 1 x 0.5...1 x 3.3 mm² (AWG 20...AWG 12) solid without cable end screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 14) flexible with cable end
electrical durability100000 cycles
mechanical durability10000000 cycles
Kompatibilnostna kodaRM22
Širina22.5 mm
tightening torque0.6-1 N.m conforming to IEC 60947-1
[Us] rated supply voltage200...240 V AC
Omejitve napajalne napetosti160-288 V AC
contacts materialcadmium free
housing materialself-extinguishing plastic
repeat accuracy+/- 0.5 % for input and measurement circuit +/- 3 % for time delay
status LEDLED (yellow)relay ON: LED (green)power ON:
insulation resistance> 100 MOhm at 500 V DC conforming to IEC 60255-27
mounting positionany position
power consumption in VA10-10 VA at 240 V AC 60 Hz
safety reliability dataMTTFd = 388.1 years B10d = 350000
supply frequency50...60 Hz +/- 10 %
overvoltage categoryIII conforming to IEC 60664-1 III conforming to UL 508
maximum switching current8 A AC
response time<= 300 ms
minimum switching current10 mA at 5 V DC
Omejitve napetosti regulacijskega vezja- 20 % + 20 % Un
maximum switching voltage250 V AC
utilisation categoryAC-15 conforming to IEC 60947-5-1 DC-13 conforming to IEC 60947-5-1 AC-1 conforming to IEC 60947-4-1 DC-1 conforming to IEC 60947-4-1
hysteresis2-2 % fixed of selectable
voltage detection threshold< 100 V AC
setting accuracy of time delay10 P
voltage range200...240 V phase to phase
reset time1500 ms at maximum voltage
maximum measuring cycle150 ms measurement cycle as true rms value
switching threshold drift<= 0.05 % per degree centigrade depending permissible ambient air temperature <= 1 % within the supply voltage range
measurement error< 1 % over the whole range with voltage variation < 0.05 %/°C with temperature variation
output contacts2 C/O
setting accuracy of the switching threshold+/- 10 % of the full scale
time delay drift<= 0.05 % per degree centigrade depending permissible ambient air temperature <= 1 % within the supply voltage range
run-up delay at power-up650 ms
threshold adjustment voltage2...20 % of Un selected
Okolje
Temperatura okoliškega zraka za delovanje-20-50 °C at 60 Hz -20-60 °C at 50 Hz AC/DC
IP stopnja zaščiteIP20 (terminals) conforming to IEC 60529 IP40 (housing) conforming to IEC 60529 IP50 (front panel) conforming to IEC 60529
Stopnja onesnaženosti3 conforming to IEC 60664-1 3 conforming to UL 508
Temperatura okoliškega zraka za skladiščenje-40-70 °C
relative humidity93-97 % at 25-55 °C conforming to IEC 60068-2-30
Certifikati izdelkovCSA CCC EAC China RoHS RCM CE GL UL
StandardiEN/IEC 60255-1
Odporno proti udarcu15 gn (duration = 11 ms) for not in operation conforming to IEC 60068-2-27 5 gn (duration = 11 ms) for in operation conforming to IEC 60068-2-27
Odpornost proti vibracijam0.075 mm (f= 10-58.1 Hz) not in operation conforming to IEC 60068-2-6 1 gn (f= 10-58.1 Hz) not in operation conforming to IEC 60068-2-6 0.035 mm (f= 58.1-150 Hz) in operation conforming to IEC 60068-2-6 0.5 gn (f= 58.1-150 Hz) in operation conforming to IEC 60068-2-6
Elektromagnetna kompatibilnostimmunity for residential, commercial and light-industrial environments conforming to EN/IEC 61000-6-1 surge immunity test - test level: 4 kV level 4 (common mode) conforming to IEC 61000-4-5 surge immunity test - test level: 2 kV level 4 (differential mode) conforming to IEC 61000-4-5 conducted and radiated emissions class B group 1 conforming to CISPR 11 conducted and radiated emissions class B conforming to CISPR 22 immunity for industrial environments conforming to EN/IEC 61000-6-2 emission standard for residential, commercial and light-industrial environments conforming to EN/IEC 61000-6-3 emission standard for industrial environments conforming to EN/IEC 61000-6-4 electrostatic discharge - test level: 6 kV level 3 (contact discharge) conforming to IEC 61000-4-2 electrostatic discharge - test level: 8 kV level 3 (air discharge) conforming to IEC 61000-4-2 radiated radio-frequency electromagnetic field immunity test - test level: 10 V/m level 3 conforming to IEC 61000-4-3 electrical fast transient/burst immunity test - test level: 4 kV level 4 (direct) conforming to IEC 61000-4-4 electrical fast transient/burst immunity test - test level: 2 kV level 4 (capacitive coupling) conforming to IEC 61000-4-4
immunity to microbreaks10 ms
dielectric test voltage2.5 kV, 1 min AC 50 Hz conforming to IEC 60255-27