Menu
Vaša košarica

RM22TA33 Schneider Electric

RM22TA33  Schneider Electric
RM22TA33 Schneider Electric

Opis

three-Phase Asymmetry control relay 380…480Vac, 2 C/O

Tehnične lastnosti

Glavno
Serija izdelkaZelio Control
Izdelek ali sestavni delmodular measurement and control relays
network number of phases3 phases
time delay typeadjustable 0.1...30 s, +/- 10 % of the full scale value on crossing the threshold Tt
measurement range380...480 V voltage AC
switching capacity in VA2000 VA
relay nameRM22TA
relay typecontrol relay
relay monitored parametersphase sequence phase failure detection asymmetry
Komplementarno
mounting support35 mm DIN rail conforming to EN/IEC 60715
Teža izdelka0.09 kg
Povezave - terminaliscrew terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end screw terminals, 1 x 0.5...1 x 3.3 mm² (AWG 20...AWG 12) solid without cable end screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 14) flexible with cable end
electrical durability100000 cycles
mechanical durability10000000 cycles
Kompatibilnostna kodaRM22
Širina22.5 mm
tightening torque0.6-1 N.m conforming to IEC 60947-1
[Us] rated supply voltage380...480 V AC
Omejitve napajalne napetosti304-576 V AC
contacts materialcadmium free
housing materialself-extinguishing plastic
repeat accuracy+/- 0.5 % for input and measurement circuit +/- 3 % for time delay
status LEDLED (yellow)relay ON: LED (green)power ON:
insulation resistance> 100 MOhm at 500 V DC conforming to IEC 60255-27
mounting positionany position
power consumption in VA15-15 VA at 480 V AC 60 Hz
safety reliability dataMTTFd = 388.1 years B10d = 350000
supply frequency50...60 Hz +/- 10 %
overvoltage categoryIII conforming to IEC 60664-1 III conforming to UL 508
maximum switching current8 A AC
response time<= 300 ms
minimum switching current10 mA at 5 V DC
Omejitve napetosti regulacijskega vezja- 20 % + 20 % Un
maximum switching voltage250 V AC
utilisation categoryAC-15 conforming to IEC 60947-5-1 DC-13 conforming to IEC 60947-5-1 AC-1 conforming to IEC 60947-4-1 DC-1 conforming to IEC 60947-4-1
hysteresis2-2 % fixed of selectable
voltage detection threshold< 100 V AC
setting accuracy of time delay10 P
voltage range380...480 V phase to phase
reset time1500 ms at maximum voltage
maximum measuring cycle150 ms measurement cycle as true rms value
switching threshold drift<= 0.05 % per degree centigrade depending permissible ambient air temperature <= 1 % within the supply voltage range
measurement error< 1 % over the whole range with voltage variation < 0.05 %/°C with temperature variation
output contacts2 C/O
setting accuracy of the switching threshold+/- 10 % of the full scale
time delay drift<= 0.05 % per degree centigrade depending permissible ambient air temperature <= 1 % within the supply voltage range
run-up delay at power-up650 ms
adjustment of asymmetry threshold5...15 % of Un selected
threshold adjustment voltage2...20 % of Un selected
Okolje
Temperatura okoliškega zraka za delovanje-20-50 °C at 60 Hz -20-60 °C at 50 Hz AC/DC
IP stopnja zaščiteIP20 (terminals) conforming to IEC 60529 IP40 (housing) conforming to IEC 60529 IP50 (front panel) conforming to IEC 60529
Stopnja onesnaženosti3 conforming to IEC 60664-1 3 conforming to UL 508
Temperatura okoliškega zraka za skladiščenje-40-70 °C
relative humidity93-97 % at 25-55 °C conforming to IEC 60068-2-30
Certifikati izdelkovGL EAC CCC CE CSA China RoHS UL RCM
StandardiEN/IEC 60255-1
Odporno proti udarcu15 gn (duration = 11 ms) for not in operation conforming to IEC 60068-2-27 5 gn (duration = 11 ms) for in operation conforming to IEC 60068-2-27
Odpornost proti vibracijam0.075 mm (f= 10-58.1 Hz) not in operation conforming to IEC 60068-2-6 1 gn (f= 10-58.1 Hz) not in operation conforming to IEC 60068-2-6 0.035 mm (f= 58.1-150 Hz) in operation conforming to IEC 60068-2-6 0.5 gn (f= 58.1-150 Hz) in operation conforming to IEC 60068-2-6
Elektromagnetna kompatibilnostimmunity for residential, commercial and light-industrial environments conforming to EN/IEC 61000-6-1 surge immunity test - test level: 4 kV level 4 (common mode) conforming to IEC 61000-4-5 surge immunity test - test level: 2 kV level 4 (differential mode) conforming to IEC 61000-4-5 conducted and radiated emissions class B group 1 conforming to CISPR 11 conducted and radiated emissions class B conforming to CISPR 22 immunity for industrial environments conforming to EN/IEC 61000-6-2 emission standard for residential, commercial and light-industrial environments conforming to EN/IEC 61000-6-3 emission standard for industrial environments conforming to EN/IEC 61000-6-4 electrostatic discharge - test level: 6 kV level 3 (contact discharge) conforming to IEC 61000-4-2 electrostatic discharge - test level: 8 kV level 3 (air discharge) conforming to IEC 61000-4-2 radiated radio-frequency electromagnetic field immunity test - test level: 10 V/m level 3 conforming to IEC 61000-4-3 electrical fast transient/burst immunity test - test level: 4 kV level 4 (direct) conforming to IEC 61000-4-4 electrical fast transient/burst immunity test - test level: 2 kV level 4 (capacitive coupling) conforming to IEC 61000-4-4
immunity to microbreaks10 ms
dielectric test voltage2.5 kV, 1 min AC 50 Hz conforming to IEC 60255-27