voltage control relay RM17-U - range 20..80 V AC

Tehnične lastnosti

Glavno
Serija izdelkaZelio Control
Izdelek ali sestavni delmodular measurement and control relays
utilisation categoryAC-12 conforming to IEC 60947-5-1 AC-13 conforming to IEC 60947-5-1 AC-14 conforming to IEC 60947-5-1 AC-15 conforming to IEC 60947-5-1 DC-12 conforming to IEC 60947-5-1 DC-13 conforming to IEC 60947-5-1 DC-14 conforming to IEC 60947-5-1
power consumption in VA0-3.9 VA AC
product specific applicationfor single-phase and DC supply
time delay typeadjustable 0.1...10 s, 0 + 10 % on crossing the threshold
measurement range20...80 V voltage AC 50/60 Hz 20...80 V voltage DC
switching capacity in VA1250 VA
relay nameRM17UBE
relay typevoltage control relay
relay monitored parametersself-powered overvoltage and undervoltage detection
minimum switching current10 mA at 5 V DC
maximum switching current5 A AC/DC
Komplementarno
mounting support35 mm symmetrical DIN rail conforming to EN/IEC 60715
Teža izdelka0.08 kg
Povezave - terminaliscrew terminals, 1 x 0.5...1 x 4 mm² (AWG 20...AWG 11) solid without cable end screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end screw terminals, 1 x 0.2...2 x 2.5 mm² (AWG 24...AWG 12) flexible with cable end screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end
[Ui] Nazivna izolacijska trdnost250 V conforming to IEC 60664-1 400 V conforming to IEC 60664-1
electrical durability100000 cycles
mechanical durability30000000 cycles
Kompatibilnostna kodaRM17
local signallingLED (green)power ON: LED (yellow)relay ON:
Širina17.5 mm
tightening torque0.6-1 N.m conforming to IEC 60947-1
[Us] rated supply voltage24...48 V AC/DC 50/60 Hz +/- 10 %
Omejitve napajalne napetosti15-100 V AC/DC
operating positionany position without
housing materialself-extinguishing plastic
repeat accuracy+/- 0.5 % for input and measurement circuit +/- 1 % for time delay
insulation resistance> 500 MOhm at 500 V DC conforming to IEC 60255-5 > 500 MOhm at 500 V DC conforming to IEC 60664-1
safety reliability dataMTTFd = 502.2 years B10d = 470000
overvoltage categoryIII conforming to IEC 60664-1
measurement accuracy+/- 10 % of the full scale value
maximum switching voltage250 V AC/DC
maximum power consumption in W1.6 W DC
hysteresis3-3 % fixed of threshold setting
nominal output current5 A
reset time1500 ms time delay
functionalityovervoltage and undervoltage detection
immunity to microbreaks20 ms
operating rate<= 360 operations/hour full load
maximum measuring cycle150 ms measurement cycle as true rms value
measurement error< 1 % over the whole range with voltage variation 0.2 %/°C with temperature variation
output contacts1 C/O
run-up delay at power-up100 ms DC 500 ms AC
polaritynon reversible polarity on DC supply
quality labelsCE
control circuit frequency50...60 Hz +/- 10 %
Okolje
Temperatura okoliškega zraka za delovanje-20-50 °C
IP stopnja zaščiteIP20 (terminals) conforming to IEC 60529 IP30 (casing) conforming to IEC 60529
Stopnja onesnaženosti3 conforming to IEC 60664-1
Temperatura okoliškega zraka za skladiščenje-40-70 °C
relative humidity95-95 % at 55-55 °C conforming to IEC 60068-2-30
Certifikati izdelkovC-Tick GOST GL CSA UL
StandardiEN/IEC 60255-6
Odporno proti udarcu5 gn conforming to IEC 60068-2-27
Odpornost proti vibracijam0.35 mm (f= 5-57.6 Hz) conforming to IEC 60068-2-6 1 gn (f= 57.6-150 Hz) conforming to IEC 60255-21-1
Elektromagnetna kompatibilnostemission standard for industrial environments conforming to EN/IEC 61000-6-4 emission standard for residential, commercial and light-industrial environments conforming to EN/IEC 61000-6-3 immunity for industrial environments conforming to NF EN/IEC 61000-6-2
directives73/23/EEC - low voltage directive 89/336/EEC - electromagnetic compatibility
non-dissipating shock wave4 kV conforming to IEC 60255-5 4 kV conforming to IEC 60664-1 4 kV conforming to IEC 61000-4-5
dielectric test voltage2 kV, 1 min AC 50 Hz conforming to IEC 60255-5 2 kV, 1 min AC 50 Hz conforming to IEC 60664-1