Menu
Vaša košarica

RM17TU00 Schneider Electric

RM17TU00  Schneider Electric
RM17TU00 Schneider Electric

Opis

multifunction control relay RM17-TU - range 183..528 V AC

Tehnične lastnosti

Glavno
Serija izdelkaZelio Control
Izdelek ali sestavni delmodular measurement and control relays
product specific applicationfor 3-phase supply
time delay typeadjustable 0.1...10 s, +/- 10 % of the full scale value
measurement range208...480 V voltage AC
switching capacity in VA1250 VA
relay nameRM17TU
relay typemultifunction control relay
relay monitored parametersundervoltage detection phase sequence phase failure detection
Komplementarno
mounting support35 mm symmetrical DIN rail conforming to EN/IEC 60715
Teža izdelka0.13 kg
Povezave - terminaliscrew terminals, 1 x 0.5...1 x 4 mm² (AWG 20...AWG 11) solid without cable end screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 12) flexible with cable end screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end
[Ui] Nazivna izolacijska trdnost400 V conforming to IEC 60664-1
electrical durability100000 cycles
mechanical durability30000000 cycles
Kompatibilnostna kodaRM17
local signallingLED (green)power ON: LED (yellow)relay ON:
Širina17.5 mm
tightening torque0.6-1 N.m conforming to IEC 60947-1
Omejitve napajalne napetosti183-528 V AC
operating positionany position without
housing materialself-extinguishing plastic
OznačevanjeCE
repeat accuracy0.5 % for input and measurement circuit 3 % for time delay
insulation resistance> 500 MOhm at 500 V DC conforming to IEC 60255-5 > 500 MOhm at 500 V DC conforming to IEC 60664-1
power consumption in VA0-22 VA at 400 V AC 50 Hz
safety reliability dataMTTFd = 502.2 years B10d = 470000
supply frequency50/60 Hz +/- 10 %
overvoltage categoryIII conforming to IEC 60664-1
maximum switching current5 A AC 5 A DC
response time< 200 ms (in the event of a fault)
minimum switching current10 mA at 5 V DC
Omejitve napetosti regulacijskega vezja- 12 % + 10 % Un
maximum switching voltage250 V AC 250 V DC
phase failure sensitivity0.7 Un
utilisation categoryAC-12 conforming to IEC 60947-5-1 AC-13 conforming to IEC 60947-5-1 AC-14 conforming to IEC 60947-5-1 AC-15 conforming to IEC 60947-5-1 DC-12 conforming to IEC 60947-5-1 DC-13 conforming to IEC 60947-5-1
hysteresis2-2 %
nominal output current5 A
voltage range208...480 V phase to phase
reset time1500 ms time delay
functionalityundervoltage detection
operating rate<= 360 operations/hour full load
maximum measuring cycle150 ms measurement cycle as true rms value
measurement error< 0.05 %/°C with temperature variation < 1 % over the whole range with voltage variation
output contacts1 C/O
run-up delay at power-up650 ms
control circuit frequency50...60 Hz +/- 10 %
adjustment of asymmetry threshold5...15 % of Un selected
threshold adjustment voltage-2...-12 % in the range 208 V AC -2...-17 % in the range 220 V AC 2...20 % of Un selected +2...+17 % in the range 480 V AC
measurement voltage limits183-528 V AC
Okolje
Temperatura okoliškega zraka za delovanje-20-50 °C
IP stopnja zaščiteIP20 (terminals) conforming to IEC 60529 IP30 (casing) conforming to IEC 60529
Stopnja onesnaženosti3 conforming to IEC 60664-1
Temperatura okoliškega zraka za skladiščenje-40-70 °C
relative humidity95-95 % at 55-55 °C conforming to IEC 60068-2-30
Certifikati izdelkovGL GOST UL C-Tick CSA
StandardiEN/IEC 60255-1
Odporno proti udarcu15 gn for 11 ms conforming to IEC 60255-21-1
Odpornost proti vibracijam0.35 mm (f= 5-57.6 Hz) conforming to IEC 60068-2-6 1 gn (f= 57.6-150 Hz) conforming to IEC 60255-21-1
Elektromagnetna kompatibilnostemission standard for industrial environments conforming to EN/IEC 61000-6-4 emission standard for residential, commercial and light-industrial environments conforming to EN/IEC 61000-6-3 immunity for industrial environments conforming to EN/IEC 61000-6-2
directives73/23/EEC - low voltage directive 89/336/EEC - electromagnetic compatibility
non-dissipating shock wave4 kV conforming to IEC 60255-5 4 kV conforming to IEC 60664-1 4 kV conforming to IEC 61000-4-5
dielectric test voltage2 kV, 1 min AC 50 Hz conforming to IEC 60255-5 2 kV, 1 min AC 50 Hz conforming to IEC 60664-1