phase control relay RM17-T - range 183..528 V AC

Tehnične lastnosti

Glavno
Serija izdelkaZelio Control
Izdelek ali sestavni delmodular measurement and control relays
product specific applicationfor 3-phase supply
time delay typewithout
measurement range208...480 V voltage AC
switching capacity in VA1250 VA
relay nameRM17TG
relay typecontrol relay
relay monitored parametersphase sequence phase failure detection
Komplementarno
mounting support35 mm symmetrical DIN rail conforming to EN/IEC 60715
Teža izdelka0.13 kg
Povezave - terminaliscrew terminals, 1 x 0.5...1 x 4 mm² (AWG 20...AWG 11) solid without cable end screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 12) flexible with cable end screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end
[Ui] Nazivna izolacijska trdnost400 V conforming to IEC 60664-1
electrical durability100000 cycles
mechanical durability30000000 cycles
Kompatibilnostna kodaRM17
local signallingLED (yellow)relay ON:
Širina17.5 mm
tightening torque0.6-1 N.m conforming to IEC 60947-1
Omejitve napajalne napetosti183-528 V AC
operating positionany position without
housing materialself-extinguishing plastic
OznačevanjeCE
insulation resistance> 500 MOhm at 500 V DC conforming to IEC 60255-5 > 500 MOhm at 500 V DC conforming to IEC 60664-1
power consumption in VA0-22 VA at 400 V AC 50 Hz
safety reliability dataMTTFd = 924.6 years B10d = 850000
supply frequency50/60 Hz +/- 10 %
overvoltage categoryIII conforming to IEC 60664-1
response time<= 130 ms (in the event of a fault)
minimum switching current10 mA at 5 V DC
Omejitve napetosti regulacijskega vezja- 12 % + 10 % Un
maximum switching voltage250 V AC 250 V DC
utilisation categoryAC-12 conforming to IEC 60947-5-1 AC-13 conforming to IEC 60947-5-1 AC-14 conforming to IEC 60947-5-1 AC-15 conforming to IEC 60947-5-1 DC-12 conforming to IEC 60947-5-1 DC-13 conforming to IEC 60947-5-1
voltage detection threshold< 100 V AC
nominal output current5 A
voltage range183...528 V
operating rate<= 360 operations/hour full load
output contacts1 C/O
run-up delay at power-up650 ms
control circuit frequency50...60 Hz +/- 10 %
measurement voltage limits183-528 V AC
Okolje
Temperatura okoliškega zraka za delovanje-20-50 °C
IP stopnja zaščiteIP20 (terminals) conforming to IEC 60529 IP30 (casing) conforming to IEC 60529
Stopnja onesnaženosti3 conforming to IEC 60664-1
Temperatura okoliškega zraka za skladiščenje-40-70 °C
relative humidity95-95 % at 55-55 °C conforming to IEC 60068-2-30
Certifikati izdelkovC-Tick GL CSA UL GOST
StandardiEN/IEC 60255-1
Odporno proti udarcu15 gn for 11 ms conforming to IEC 60255-21-1
Odpornost proti vibracijam0.35 mm (f= 5-57.6 Hz) conforming to IEC 60068-2-6 1 gn (f= 57.6-150 Hz) conforming to IEC 60255-21-1
Elektromagnetna kompatibilnostemission standard for industrial environments conforming to EN/IEC 61000-6-4 emission standard for residential, commercial and light-industrial environments conforming to EN/IEC 61000-6-3 immunity for industrial environments conforming to EN/IEC 61000-6-2
directives73/23/EEC - low voltage directive 89/336/EEC - electromagnetic compatibility
non-dissipating shock wave4 kV
dielectric test voltage2 kV, 1 min AC 50 Hz