Menu
Vaša košarica

RENF22R2MMW Schneider Electric

RENF22R2MMW  Schneider Electric
RENF22R2MMW Schneider Electric

Opis

Zelio Timer Relay - Modular

Tehnične lastnosti

Glavno
Serija izdelkaZelio Time
Izdelek ali sestavni delmodular timing relay
Kratko ime napraveRENF22
software designationZelio NFC (downloadable from Google Play store)
software versionV4.4 and above
operating systemAndroid
Komplementarno
mounting support35 mm DIN rail conforming to EN/IEC 60715
Teža izdelka0.0904 kg
Povezave - terminaliscrew terminals, 1 x 0.5...1 x 3.3 mm² (AWG 20...AWG 12) solid without cable end screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 14) flexible with cable end screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end
electrical durability100000 cycles for resistive load, 8 A at 250 V, AC
mechanical durability10000000 cycles
local signallingLED Un: (steady), green for power ON LED R1: (steady), amber for relay energised LED R2: (steady), amber for relay energised LED pairing: (steady), green for communication status LED Un: (fast blinking), green for diagnosis mode LED R1: (blinking), amber for timing in progress LED R2: (blinking), amber for timing in progress
[Uimp] rated impulse withstand voltage5 kV 1.2/50 µs conforming to IEC 60664-1
Širina22.5 mm
tightening torque0.6-1 N.m conforming to IEC 60947-1 5.3-8.8 lbf.in conforming to IEC 60947-1
[Us] rated supply voltage24...240 V AC/DC
product compatibilityNFC enabled mobile device
contacts type and composition2 C/O timed contact, cadmium free 1 C/O timed and instantaneous contact, cadmium free
housing materialself-extinguishing
input voltage<= 2.4 V
repeat accuracy+/- 0.2 % for 10 s...999 h time delay range +/- 0.5 % for 100 ms...10 s time delay range
maximum delay response100 ms
insulation resistance100 MOhm at 500 V DC conforming to IEC 60664-1
mounting positionany position
power consumption in W1.5 W at 240 V DC 0.6 W at 24 V DC
power consumption in VA3-3 VA at 240 V AC
safety reliability dataMTTFd = 227.5 years 100 % duty cycle continuous operating condition at 30 °C
supply frequency50...60 Hz +/- 5 %
overvoltage categoryIII conforming to IEC 60664-1
time delay range0.1 s...999 h
maximum switching current8 A
discrete output typerelay
response time2 s
minimum switching current10 mA at 5 V
maximum switching voltage250 V
nominal power2.0E-4 mW
nominal output current8 A
setting accuracy of time delay+/- 1 % for 1...999 h time delay range at 25 °C +/- 2 % for 1 h time delay range at 25 °C +/- 20 ms for 100 ms...10 s time delay range at 25 °C
creepage distance4 kV/3 conforming to IEC 60664-1
voltage range0.85...1.1 Un
reset time120 ms on de-energisation
voltage drift+/- 0.2 %/V
temperature drift+/- 0.05 %/°C
time delay typeTt Ak Ah Di Pt H At Dt Ad A Qt N Li L Qtt O Ht Lit C Lt W Tl P Ac Dit B D Bw
operating distance10 mm
maximum operating frequency13.56 MHz
switching capacity in VA2000 VA
minimum pulse duration100 ms with load in parallel 60 ms no-load
Okolje
Temperatura okoliškega zraka za delovanje-20-60 °C
IP stopnja zaščiteIP40 housing: conforming to IEC 60529 IP40 front face: conforming to IEC 60529 IP20 terminals: conforming to IEC 60529
Stopnja onesnaženosti3 conforming to IEC 60664-1
Temperatura okoliškega zraka za skladiščenje-40-70 °C
relative humidity95-95 % at 25-55 °C
Certifikati izdelkovCE CSA KC UL CCC EAC DNV-GL
StandardiEN 61000-6-1 EN 61000-6-2 EN 61000-6-4 EN 61812-1 EN 61000-6-3
Odporno proti udarcu15 gn not operating for 11 ms conforming to IEC 60068-2-27 5 gn in operation for 11 ms conforming to IEC 60068-2-27
Odpornost proti vibracijam20 m/s² (f= 10-150 Hz) conforming to IEC 60068-2-6
Elektromagnetna kompatibilnostelectrostatic discharge immunity test - test level: 6 kV level 3 (contact discharge) conforming to EN/IEC 61000-4-2 electrostatic discharge immunity test - test level: 8 kV level 3 (air discharge) conforming to EN/IEC 61000-4-2 fast transients immunity test - test level: 1 kV level 3 (capacitive connecting clip) conforming to IEC 61000-4-4 fast transients immunity test - test level: 2 kV level 3 (direct contact) conforming to IEC 61000-4-4 surge immunity test - test level: 1 kV level 3 (differential mode) conforming to IEC 61000-4-5 surge immunity test - test level: 2 kV level 3 (common mode) conforming to IEC 61000-4-5 radiated radio-frequency electromagnetic field immunity test - test level: 10 V level 3 (0.15...80 MHz) conforming to IEC 61000-4-6 electromagnetic field immunity test - test level: 10 V/m level 3 (80 MHz...1 GHz) conforming to IEC 61000-4-3 immunity to microbreaks and voltage drops - test level: 30 % (500 ms) conforming to IEC 61000-4-11 immunity to microbreaks and voltage drops - test level: 100 % (20 ms) conforming to IEC 61000-4-11 radiated emission class B conforming to EN 55022 conducted emission class A conforming to EN 55022 electromagnetic field immunity test - test level: 3 V/m level 2 (1.4 GHz...2 GHz) conforming to IEC 61000-4-3 electromagnetic field immunity test - test level: 1 V/m level 1 (2...2.7 GHz) conforming to IEC 61000-4-3
directives2014/35/EU - low voltage directive 2014/53/EU - radio equipment directive 2014/30/EU - electromagnetic compatibility
dielectric strength2.5 kV for 1 mA/1 minute at 50 Hz with between relay output and power supply with basic insulation with basic insulation
immunity to microbreaks10 ms