Menu
Vaša košarica

LV432732 Schneider

LV432732  Schneider
LV432732 Schneider

Opis

circuit breaker Vigicompact NSX 400F, 36 kA at 415 VAC, Micrologic 2.3 trip unit 400 A, add-on Vigi MB module, 4P 4d

Tehnične lastnosti

Glavno
[In] rated current400 A at 40 °C
Serija izdelkaNSX400...630
network typeAC
breaking capacity codeF 36 kA 415 V AC
Izdelek ali sestavni delcircuit breaker with Vigi add-on
product nameCompact NSX
utilisation categorycategory A
Skupina izdelkovCompact
breaking capacity40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 85 kA at 240 V AC 50/60 Hz conforming to UL 508 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 480 V AC 50/60 Hz conforming to UL 508 20 kA at 600 V AC 50/60 Hz conforming to UL 508 20 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
suitability for isolationyes conforming to EN 60947-2 yes conforming to IEC 60947-2
Opis polov4P
Aplikacija napravedistribution
Kratko ime napraveVigiCompact NSX400F
trip unit technologyelectronic
network frequency50/60 Hz
[Ics] rated service breaking capacity40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
trip unit nameMicrologic 2.3
protected poles description3t + N/2 4t 3t
neutral positionleft
earth-leakage add-on module nameMB
[Ue] rated operational voltage440 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage8 kV
[Ui] rated insulation voltage800 V AC 50/60 Hz
pollution degree3 conforming to IEC 60664-1
trip unit protection functionsLSoI
Komplementarno
Višina355 mm
earth-leakage protectionwith
mounting supportbackplate
Teža izdelka7.9 kg
control typetoggle
mounting modefixed
electrical durability12000 cycles 440 V In/2 conforming to IEC 60947-2 3000 cycles 690 V In conforming to IEC 60947-2 6000 cycles 440 V In conforming to IEC 60947-2 6000 cycles 690 V In/2 conforming to IEC 60947-2
mechanical durability15000 cycles
Kompatibilnostna kodaNSX400
local signallingLED 105 % Ir LED 90 % Ir LED ready
Širina180 mm
Globina110 mm
long time pick-up adjustment type Iradjustable 9 settings
upside connectionfront
downside connectionfront
protection typeL : for overload protection (long time) So : for short time short-circuit protection with fixed delay I : for instantaneous short-circuit protection
connection pitch45 mm
earth-leakage protection classclass A
instantaneous pick-up adjustment range4800 A
long time delay adjustment typefixed
instantaneous pick-up adjustment type Iifixed
residual earth-leakage sensitity adjustment typefixed
neutral protection setting0.5 x Ir (3t + N/2) 1 x Ir (4t) no protection (3t)
long time pick-up adjustment range0.9...1 x Io
[IΔn] residual earth-leakage sensitive adjustment0.3-0.3 A
residual earth-leakage time delay adjustment typeadjustable 4 settings
trip unit rating400-400 A at 40 °C
thermal memory20 minutes before and after tripping
[tr] long-time delay adjustment range16-16 s at 6 x Ir
short-time delay adjustment typefixed
[Isd] short-time pick-up adjustment range1.5...10 x Ir
short-time pick-up adjustment type Isdadjustable 9 settings
Okolje
Temperatura okoliškega zraka za delovanje-35-70 °C
IP stopnja zaščiteIP40 conforming to IEC 60529
Temperatura okoliškega zraka za skladiščenje-55-85 °C
overvoltage categoryclass II
IK stopnja zaščiteIK07 conforming to IEC 62262
Certifikati izdelkovMarine CCC EAC
StandardiEN/IEC 60947 UL 508
electrical shock protection classclass II