LV426407 Schneider

LV426407 Schneider
Opis
circuit breaker Compact NSXm N (50 kA at 415 VAC), 3P, 100 A rating TMD trip unit, EverLink connectors
Tehnične lastnosti
| Glavno | |
| Serija izdelka | Compact |
| Izdelek ali sestavni del | circuit breaker |
| product name | Compact NSXm |
| Skupina izdelkov | Compact |
| Aplikacija naprave | distribution protection |
| Kratko ime naprave | NSXm 100N |
| Komplementarno | |
| network frequency | 50/60 Hz |
| [Ics] rated service breaking capacity | 90 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
| 9 mm pitches | 9 module |
| Povezave - terminali | 1 Everlink lug wire size 2.5-95 mm², rigid or stranded aluminium/copper 1 Everlink lug wire size 2.5-70 mm², flexible copper |
| wire stripping length | 20 mm |
| control type | toggle |
| [Ui] Nazivna izolacijska trdnost | 800 V conforming to IEC 60947-2 |
| mounting mode | by screws (plate) clip-on (DIN rail) |
| local signalling | flag (green)presence of auxiliary contacts: |
| tightening torque | 5-5 N.m for 2.5-10 mm² 9-9 N.m for 16-95 mm² |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| long time pick-up adjustment type Ir | adjustable |
| magnetic tripping current | 1500-1500 A |
| [In] rated current | 100 A |
| protection type | short-circuit protection (magnetic) overload protection (thermal) |
| breaking capacity | Icu 90 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 Icu 50 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 Icu 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
| breaking capacity code | N 50 kA 415 V AC |
| connection pitch | 35 mm with spreaders 27 mm without spreaders |
| long time delay adjustment type | fixed |
| long time pick-up adjustment range | 0.7...1 x In |
| poles description | 3P 3d |
| network type | AC |
| utilisation category | category A |
| suitability for isolation | yes conforming to IEC 60947-2 |
| trip unit rating | 100-100 A at 40 °C |
| trip unit protection functions | LI |
| short-time delay adjustment type | fixed |
| short-time pick-up adjustment type Isd | fixed |
| Število rež | 1 slot(s) for auxiliary switch OF 1 slot(s) for alarm switch SD 1 slot(s) for voltage release MN or MX |
| trip unit technology | thermal-magnetic |
| trip unit name | TM-D |
| magnetic hold current | 1000 A |
| Okolje | |
| Temperatura okoliškega zraka za delovanje | -25-70 °C |
| IP stopnja zaščite | front cover: IP40 conforming to IEC 60529 |
| Stopnja onesnaženosti | 3 conforming to IEC 60947-1 |
| Temperatura okoliškega zraka za skladiščenje | -40-85 °C |
| Nadmorska višina delovanja | 2000 m without derating 5000 m with derating |
| IK stopnja zaščite | IK07 conforming to IEC 62262 |
| Certifikati izdelkov | CCC EAC Marine |
| Standardi | EN/IEC 60947 |
| Višina | 137 mm |
| net weight | 1.06 kg |
| Širina | 81 mm |
| Globina | 80 mm |
| quality labels | CE |
| Količina na set/komplet | set of 1 |
| colour | grey (RAL 7016) |
| electrical durability | 10000 cycles conforming to IEC 947-1 Annex F ed 5.2 for In at 440 V |
| mechanical durability | 20000 cycles conforming to IEC 947-1 Annex K ed 5.2 In |