Menu
Vaša košarica

48364 Schneider Electric

48364  Schneider Electric
48364 Schneider Electric

Opis

control unit Micrologic 6.0 P, for Masterpact NW drawout, LSIG protections

Tehnične lastnosti

Glavno
Serija izdelkaMasterpact NW
network typeAC
Izdelek ali sestavni delcontrol unit
product nameMicrologic
Skupina izdelkovMasterpact
Opis polov3P 4P
Aplikacija napravedistribution
trip unit technologyelectronic
network frequency50/60 Hz
trip unit nameMicrologic 6.0 P
trip unit rating800-800 A at 50 °C 1000-1000 A at 50 °C 1250-1250 A at 50 °C 1600-1600 A at 50 °C 2000-2000 A at 50 °C 2500-2500 A at 50 °C 3200-3200 A at 50 °C 4000-4000 A at 50 °C 5000-5000 A at 50 °C 6300-6300 A at 50 °C
protected poles description4t 3t 3t + N/2
protection typeinstantaneous short-circuit protection short time short-circuit protection earth fault overload protection (long time)
Združljivost serije/obsegaMasterpact NW08...40 Masterpact NW40b...63 Masterpact NW H10 Masterpact NW H2 corrosion protection
trip unit protection functionsselective + earth-fault protection
Komplementarno
mounting modedrawout
long time pick-up adjustment type Iradjustable 9 settings
instantaneous pick-up adjustment rangeoff 2...15 x In
long time delay adjustment typeadjustable 9 settings
instantaneous pick-up adjustment type Iiadjustable 9 settings
long time pick-up adjustment range0.4...1 x In
display typedigital display
thermal memory20 mn
[tr] long-time delay adjustment range0.7-16.6 s 7.2 x Ir 0.7-24 s 6 x Ir 12.5-600 s 1.5 x Ir
type of measurementpower meter
zone selective interlocking ZSIwith
short-time delay adjustment typeadjustable
[tsd] short-time delay adjustment range0-0.4 s I²t=off 0.1-0.4 s I²t=on
[Isd] short-time pick-up adjustment range1.5...10 x Ir
short-time pick-up adjustment type Isdadjustable 9 settings
communication of datameasurement readout protection and alarm settings maintenance indicators
[Ig] ground-fault pick-up adjustment range0.2...1 x In for 400 A < In < 1250 A 0.3...1 x In for In <= 400 A 500...1200 A for In >= 1250 A
ground-fault time delay adjustment type -tgadjustable
ground-fault pick-up adjustment typeadjustable 9 settings
[tg] ground-fault time delay adjustment range0-0.4 s I²t=off 0.1-0.4 s I²t=on
Okolje
Temperatura okoliškega zraka za delovanje-25-70 °C
Temperatura okoliškega zraka za skladiščenje-25-85 °C