Opis

motor controller LTMR TeSys T - 24 V DC 27 A for DeviceNet

Tehnične lastnosti

Glavno
Izdelek ali sestavni delmotor controller
product nameTeSys T
Skupina izdelkovTeSys
Aplikacija napraveequipment monitoring and control
Kratko ime napraveLTMR
[Us] Nazivna napajalna npetost24 V DC
communication port protocolDeviceNet
supply voltage limits20.4-26.24 V DC
current consumption56...127 mA
bus typeDeviceNet ISO 1198 interface, addressing 1...64, transmission rate 125...500 kbit/s, terminal block with 4 twisted shielded pairs cable
measurement current1.35-27 A
Komplementarno
Višina61 mm
Teža izdelka0.53 kg
Povezave - terminalicontrol circuit: connector 1 cable(s) 0.25-2.5 mm² (AWG 24...AWG 14) flexible with cable end control circuit: connector 1 cable(s) 0.2-2.5 mm² (AWG 24...AWG 14) flexible without cable end control circuit: connector 1 cable(s) 0.25-2.5 mm² (AWG 24...AWG 14) flexible without cable end control circuit: connector 1 cable(s) 0.2-2.5 mm² (AWG 24...AWG 14) solid without cable end control circuit: connector 2 cable(s) 0.2-1 mm² (AWG 24...AWG 14) flexible with cable end control circuit: connector 2 cable(s) 0.2-1.5 mm² (AWG 24...AWG 14) flexible without cable end control circuit: connector 2 cable(s) 0.5-1.5 mm² (AWG 24...AWG 14) flexible without cable end control circuit: connector 2 cable(s) 0.2-1 mm² (AWG 24...AWG 14) solid without cable end
[Ui] Nazivna izolacijska trdnost690 V conforming to EN/IEC 60947-1 690 V conforming to CSA C22.2 No 14 690 V conforming to UL 508
Kompatibilnostna kodaLTMR
[Uimp] rated impulse withstand voltage6 kV current or voltage measurement circuit conforming to EN/IEC 60947-4-1 0.8 kV communication circuit conforming to EN/IEC 60947-4-1 0.8 kV supply, inputs and outputs conforming to EN/IEC 60947-4-1
Širina91 mm
Globina122.5 mm
tightening torquecontrol circuit: 0.5-0.6 N.m flat screwdriver 3 mm
protection typepower factor variation thermal protection locked rotor overload (long time) phase unbalance reverse polarity protection load fluctuation overload earth-leakage protection phase failure thermal overload protection
contacts type and composition1 NO + 1 NC fault signal 3 NO
connection pitch5.08 mm
maximum operating rate1800 cyc/h
input current7 mA
overvoltage categoryIII
electromagnetic compatibilityelectrostatic discharge, 3, 8 kV air, 6 kV contact, conforming to EN/IEC 61000-4-2 control circuit: surges (common mode), 1 kV, conforming to EN/IEC 61000-4-5 communication: surges (common mode), 2 kV, conforming to EN/IEC 61000-4-5 relay outputs and supply: surges (serial mode), 2 kV, conforming to EN/IEC 61000-4-5 relay outputs and supply: surges (common mode), 4 kV, conforming to EN/IEC 61000-4-5 radiated RF fields, 3, 10 V/m, conforming to EN/IEC 61000-4-3 fast transients immunity test (other circuits), level 3, 2 kV, conforming to EN/IEC 61000-4-4 fast transients immunity test (on supply and relay outputs), level 4, 4 kV, conforming to EN/IEC 61000-4-4 voltage dips and interruptions immunity test, 70 %, 500 ms, conforming to EN/IEC 61000-4-11 conducted RF disturbances, 10 V, conforming to EN/IEC 61000-4-6 temperature sensor: surges (serial mode), 0.5 kV, conforming to EN/IEC 61000-4-5 temperature sensor: surges (common mode), 1 kV, conforming to EN/IEC 61000-4-5 control circuit: surges (serial mode), 1 kV, conforming to EN/IEC 61000-4-5
measurement accuracy5...15 % earth fault current internal measurement 1 % voltage (100...830 V) 3 % power factor 5 % earth fault current external measurement +/- 30 min/year internal clock 0,02 temperature 1 % current 5 % active and reactive power
pollution degree3
associated fuse rating4 A gG for output 0.5 A gG for control circuit
web servicesweb server
short-circuit withstand100 kA conforming to EN/IEC 60947-4-1
current state 1 guaranteedlogic input: < 15 V and 2...15 mA for 15 ms
current state 0 guaranteedlogic input: < 5 V and <= 15 mA for 5 ms
load current5 A at 250 V AC for logic output 5 A at 30 V DC for logic output
permissible power480 VA (AC-15), Ie = 2 A, 500000 cycles (output) 30 W (DC-13), Ie = 1.25 A, 500000 cycles (output)
network and machine diagnosis typerunning hours counter/operating time fault recording remaining operating time before overload tripping event recording trip context information phase fault and earth fault trip counters starting current and time trip history information motor control command recording waiting time after overload tripping
logic input number6
maximum operating frequency2 Hz
metering typeaverage current Iavg phase current I1, I2, I3 RMS earth-fault current temperature imbalance current
Okolje
Temperatura okoliškega zraka za delovanje-20-60 °C
IP stopnja zaščiteIP20
Temperatura okoliškega zraka za skladiščenje-40-80 °C
Nadmorska višina delovanja<= 2000 m without derating
Certifikati izdelkovLROS (Lloyds register of shipping) RINA KERI RMRoS CSA ATEX DNV C-Tick CCC BV EAC NOM ABS UL GL
StandardiUL 508 CSA C22.2 No 14 IACS E10 IEC 60947-4-1 EN 60947-4-1
Zaščitna obdelava12 x 24 hour cycles conforming to EN/IEC 60068-2-30 48 h conforming to EN/IEC 60070-2-11 TH conforming to EN/IEC 60068
fire resistance650 °C conforming to EN/IEC 60695-2-12 960 °C conforming to UL 94
mechanical robustnessvibrations mounted on symmetrical rail: 1 Gn, 5...300 Hz conforming to EN/IEC 60068-2-6 vibrations plate mounted: 4 Gn, 5...300 Hz conforming to EN/IEC 60068-2-6 shocks half sine wave acceleration: 15 Gn for 11 ms conforming to EN/IEC 60068-2-27