Menu
Vaša košarica

LTMR27CBD Schneider Electric

LTMR27CBD  Schneider Electric
LTMR27CBD Schneider Electric

Opis

motor controller LTMR TeSys T - 24 V DC 27 A for CANopen

Tehnične lastnosti

Glavno
Izdelek ali sestavni delmotor controller
product nameTeSys T
Skupina izdelkovTeSys
Aplikacija napraveequipment monitoring and control
Kratko ime napraveLTMR
[Us] Nazivna napajalna npetost24 V DC
communication port protocolCANopen
supply voltage limits20.4-26.24 V DC
current consumption56...127 mA
bus typeCANopen ISO 1198 interface, addressing 1...127, transmission rate 10...1000 kbit/s, SUB-D 9 with 4 twisted shielded pairs cable CANopen ISO 1198 interface, addressing 1...127, transmission rate 10...1000 kbit/s, terminal block with 4 twisted shielded pairs cable
measurement current1.35-27 A
Komplementarno
Višina61 mm
Teža izdelka0.53 kg
Povezave - terminalicontrol circuit: connector 1 cable(s) 0.25-2.5 mm² (AWG 24...AWG 14) flexible with cable end control circuit: connector 1 cable(s) 0.2-2.5 mm² (AWG 24...AWG 14) flexible without cable end control circuit: connector 1 cable(s) 0.25-2.5 mm² (AWG 24...AWG 14) flexible without cable end control circuit: connector 1 cable(s) 0.2-2.5 mm² (AWG 24...AWG 14) solid without cable end control circuit: connector 2 cable(s) 0.2-1 mm² (AWG 24...AWG 14) flexible with cable end control circuit: connector 2 cable(s) 0.2-1.5 mm² (AWG 24...AWG 14) flexible without cable end control circuit: connector 2 cable(s) 0.5-1.5 mm² (AWG 24...AWG 14) flexible without cable end control circuit: connector 2 cable(s) 0.2-1 mm² (AWG 24...AWG 14) solid without cable end
[Ui] Nazivna izolacijska trdnost690 V conforming to EN/IEC 60947-1 690 V conforming to CSA C22.2 No 14 690 V conforming to UL 508
Kompatibilnostna kodaLTMR
[Uimp] rated impulse withstand voltage6 kV current or voltage measurement circuit conforming to EN/IEC 60947-4-1 0.8 kV communication circuit conforming to EN/IEC 60947-4-1 0.8 kV supply, inputs and outputs conforming to EN/IEC 60947-4-1
Širina91 mm
Globina122.5 mm
tightening torquecontrol circuit: 0.5-0.6 N.m flat screwdriver 3 mm
protection typeoverload (long time) thermal protection load fluctuation locked rotor overload thermal overload protection power factor variation phase unbalance reverse polarity protection earth-leakage protection phase failure
contacts type and composition1 NO + 1 NC fault signal 3 NO
connection pitch5.08 mm
maximum operating rate1800 cyc/h
input current7 mA
overvoltage categoryIII
electromagnetic compatibilityelectrostatic discharge, 3, 8 kV air, 6 kV contact, conforming to EN/IEC 61000-4-2 control circuit: surges (common mode), 1 kV, conforming to EN/IEC 61000-4-5 communication: surges (common mode), 2 kV, conforming to EN/IEC 61000-4-5 relay outputs and supply: surges (serial mode), 2 kV, conforming to EN/IEC 61000-4-5 relay outputs and supply: surges (common mode), 4 kV, conforming to EN/IEC 61000-4-5 radiated RF fields, 3, 10 V/m, conforming to EN/IEC 61000-4-3 fast transients immunity test (other circuits), level 3, 2 kV, conforming to EN/IEC 61000-4-4 fast transients immunity test (on supply and relay outputs), level 4, 4 kV, conforming to EN/IEC 61000-4-4 voltage dips and interruptions immunity test, 70 %, 500 ms, conforming to EN/IEC 61000-4-11 conducted RF disturbances, 10 V, conforming to EN/IEC 61000-4-6 temperature sensor: surges (serial mode), 0.5 kV, conforming to EN/IEC 61000-4-5 temperature sensor: surges (common mode), 1 kV, conforming to EN/IEC 61000-4-5 control circuit: surges (serial mode), 1 kV, conforming to EN/IEC 61000-4-5
measurement accuracy5...15 % earth fault current internal measurement 1 % voltage (100...830 V) 3 % power factor 5 % earth fault current external measurement +/- 30 min/year internal clock 0,02 temperature 1 % current 5 % active and reactive power
pollution degree3
associated fuse rating4 A gG for output 0.5 A gG for control circuit
web servicesweb server
short-circuit withstand100 kA conforming to EN/IEC 60947-4-1
current state 1 guaranteedlogic input: < 15 V and 2...15 mA for 15 ms
current state 0 guaranteedlogic input: < 5 V and <= 15 mA for 5 ms
load current5 A at 250 V AC for logic output 5 A at 30 V DC for logic output
permissible power480 VA (AC-15), Ie = 2 A, 500000 cycles (output) 30 W (DC-13), Ie = 1.25 A, 500000 cycles (output)
network and machine diagnosis typephase fault and earth fault trip counters trip context information waiting time after overload tripping fault recording remaining operating time before overload tripping starting current and time motor control command recording event recording running hours counter/operating time trip history information
logic input number6
maximum operating frequency2 Hz
metering typetemperature imbalance current phase current I1, I2, I3 RMS earth-fault current average current Iavg
Okolje
Temperatura okoliškega zraka za delovanje-20-60 °C
IP stopnja zaščiteIP20
Temperatura okoliškega zraka za skladiščenje-40-80 °C
Nadmorska višina delovanja<= 2000 m without derating
Certifikati izdelkovCSA DNV RINA KERI NOM BV CCC EAC ATEX ABS LROS (Lloyds register of shipping) C-Tick GL UL RMRoS
StandardiCSA C22.2 No 14 IEC 60947-4-1 EN 60947-4-1 IACS E10 UL 508
Zaščitna obdelava12 x 24 hour cycles conforming to EN/IEC 60068-2-30 48 h conforming to EN/IEC 60070-2-11 TH conforming to EN/IEC 60068
fire resistance650 °C conforming to EN/IEC 60695-2-12 960 °C conforming to UL 94
mechanical robustnessvibrations mounted on symmetrical rail: 1 Gn, 5...300 Hz conforming to EN/IEC 60068-2-6 vibrations plate mounted: 4 Gn, 5...300 Hz conforming to EN/IEC 60068-2-6 shocks half sine wave acceleration: 15 Gn for 11 ms conforming to EN/IEC 60068-2-27