Menu
Vaša košarica

LTMR100MFM Schneider Electric

LTMR100MFM  Schneider Electric
LTMR100MFM Schneider Electric

Opis

motor controller LTMR TeSys T - 100..240 V AC 100 A for Modbus

Tehnične lastnosti

Glavno
Izdelek ali sestavni delmotor controller
product nameTeSys T
Skupina izdelkovTeSys
Aplikacija napraveequipment monitoring and control
Kratko ime napraveLTMR
[Us] Nazivna napajalna npetost100...240 V AC 50/60 Hz
communication port protocolModbus
supply voltage limits93.5-264 V AC
current consumption8...62.8 mA
bus typeModbus 2-wire RS 485 interface, addressing 1...247, transmission rate 1.2...19.2 kbit/s, RJ45 with 2 shielded twisted pairs Modbus 2-wire RS 485 interface, addressing 1...247, transmission rate 1.2...19.2 kbit/s, terminal block with 2 shielded twisted pairs
measurement current5-100 A
Komplementarno
Višina61 mm
Teža izdelka0.53 kg
Povezave - terminalicontrol circuit: connector 1 cable(s) 0.25-2.5 mm² (AWG 24...AWG 14) flexible with cable end control circuit: connector 1 cable(s) 0.2-2.5 mm² (AWG 24...AWG 14) flexible without cable end control circuit: connector 1 cable(s) 0.25-2.5 mm² (AWG 24...AWG 14) flexible without cable end control circuit: connector 1 cable(s) 0.2-2.5 mm² (AWG 24...AWG 14) solid without cable end control circuit: connector 2 cable(s) 0.2-1 mm² (AWG 24...AWG 14) flexible with cable end control circuit: connector 2 cable(s) 0.2-1.5 mm² (AWG 24...AWG 14) flexible without cable end control circuit: connector 2 cable(s) 0.5-1.5 mm² (AWG 24...AWG 14) flexible without cable end control circuit: connector 2 cable(s) 0.2-1 mm² (AWG 24...AWG 14) solid without cable end
[Ui] Nazivna izolacijska trdnost690 V conforming to EN/IEC 60947-1 690 V conforming to CSA C22.2 No 14 690 V conforming to UL 508
Kompatibilnostna kodaLTMR
[Uimp] rated impulse withstand voltage4 kV supply, inputs and outputs conforming to EN/IEC 60947-4-1 6 kV current or voltage measurement circuit conforming to EN/IEC 60947-4-1 0.8 kV communication circuit conforming to EN/IEC 60947-4-1
Širina91 mm
Globina122.5 mm
tightening torquecontrol circuit: 0.5-0.6 N.m flat screwdriver 3 mm
protection typeload fluctuation earth-leakage protection overload (long time) overload locked rotor thermal protection thermal overload protection power factor variation reverse polarity protection phase failure phase unbalance
contacts type and composition1 NO + 1 NC fault signal 3 NO
connection pitch5.08 mm
maximum operating rate1800 cyc/h
input current3.1 mA at 100 V 7.5 mA at 240 V
overvoltage categoryIII
electromagnetic compatibilityelectrostatic discharge, 3, 8 kV air, 6 kV contact, conforming to EN/IEC 61000-4-2 communication: surges (common mode), 2 kV, conforming to EN/IEC 61000-4-5 relay outputs and supply: surges (serial mode), 2 kV, conforming to EN/IEC 61000-4-5 relay outputs and supply: surges (common mode), 4 kV, conforming to EN/IEC 61000-4-5 control circuit: surges (common mode), 2 kV, conforming to EN/IEC 61000-4-5 radiated RF fields, 3, 10 V/m, conforming to EN/IEC 61000-4-3 fast transients immunity test (other circuits), level 3, 2 kV, conforming to EN/IEC 61000-4-4 fast transients immunity test (on supply and relay outputs), level 4, 4 kV, conforming to EN/IEC 61000-4-4 voltage dips and interruptions immunity test, 70 %, 500 ms, conforming to EN/IEC 61000-4-11 conducted RF disturbances, 10 V, conforming to EN/IEC 61000-4-6 temperature sensor: surges (serial mode), 0.5 kV, conforming to EN/IEC 61000-4-5 temperature sensor: surges (common mode), 1 kV, conforming to EN/IEC 61000-4-5 control circuit: surges (serial mode), 1 kV, conforming to EN/IEC 61000-4-5
measurement accuracy5...15 % earth fault current internal measurement 1 % voltage (100...830 V) 3 % power factor 5 % earth fault current external measurement +/- 30 min/year internal clock 0,02 temperature 5 % active and reactive power 0,02 current
pollution degree3
associated fuse rating4 A gG for output 0.5 A gG for control circuit
web servicesweb server
short-circuit withstand100 kA conforming to EN/IEC 60947-4-1
current state 1 guaranteedlogic input: 79...264 V and >= 2 mA for 25 ms
current state 0 guaranteedlogic input: 0...40 V and <= 15 mA for 25 ms
load current5 A at 250 V AC for logic output 5 A at 30 V DC for logic output
permissible power480 VA (AC-15), Ie = 2 A, 500000 cycles (output) 30 W (DC-13), Ie = 1.25 A, 500000 cycles (output)
network and machine diagnosis typemotor control command recording starting current and time trip history information phase fault and earth fault trip counters running hours counter/operating time remaining operating time before overload tripping fault recording trip context information event recording waiting time after overload tripping
logic input number6
maximum operating frequency2 Hz
metering typetemperature earth-fault current average current Iavg imbalance current phase current I1, I2, I3 RMS
Okolje
Temperatura okoliškega zraka za delovanje-20-60 °C
IP stopnja zaščiteIP20
Temperatura okoliškega zraka za skladiščenje-40-80 °C
Nadmorska višina delovanja<= 2000 m without derating
Certifikati izdelkovLROS (Lloyds register of shipping) UL ABS ATEX EAC CCC BV RINA DNV C-Tick RMRoS CSA GL NOM KERI
StandardiIACS E10 IEC 60947-4-1 UL 508 EN 60947-4-1 CSA C22.2 No 14
Zaščitna obdelava12 x 24 hour cycles conforming to EN/IEC 60068-2-30 48 h conforming to EN/IEC 60070-2-11 TH conforming to EN/IEC 60068
fire resistance650 °C conforming to EN/IEC 60695-2-12 960 °C conforming to UL 94
mechanical robustnessvibrations mounted on symmetrical rail: 1 Gn, 5...300 Hz conforming to EN/IEC 60068-2-6 vibrations plate mounted: 4 Gn, 5...300 Hz conforming to EN/IEC 60068-2-6 shocks half sine wave acceleration: 15 Gn for 11 ms conforming to EN/IEC 60068-2-27