LTMR100EFM Schneider Electric

LTMR100EFM  Schneider Electric
LTMR100EFM Schneider Electric

Opis

motor controller LTMR TeSys T - 100..240 V AC 100 A for Ethernet TCP/IP

Tehnične lastnosti

Glavno
Izdelek ali sestavni delmotor controller
product nameTeSys T
Skupina izdelkovTeSys
Aplikacija napraveequipment monitoring and control
Kratko ime napraveLTMR
[Us] Nazivna napajalna npetost100...240 V AC 50/60 Hz
communication port protocolModbus TCP/EtherNet/IP
supply voltage limits93.5-264 V AC
current consumption8...62.8 mA
bus typeEthernet IEEE 802.3 interface, addressing 0...159, transmission rate 10...100 Mbit/s, RJ45 with 2 shielded twisted pairs
measurement current5-100 A
Komplementarno
Višina61 mm
Teža izdelka0.53 kg
Povezave - terminalicontrol circuit: connector 1 cable(s) 0.25-2.5 mm² (AWG 24...AWG 14) flexible with cable end control circuit: connector 1 cable(s) 0.2-2.5 mm² (AWG 24...AWG 14) flexible without cable end control circuit: connector 1 cable(s) 0.25-2.5 mm² (AWG 24...AWG 14) flexible without cable end control circuit: connector 1 cable(s) 0.2-2.5 mm² (AWG 24...AWG 14) solid without cable end control circuit: connector 2 cable(s) 0.2-1 mm² (AWG 24...AWG 14) flexible with cable end control circuit: connector 2 cable(s) 0.2-1.5 mm² (AWG 24...AWG 14) flexible without cable end control circuit: connector 2 cable(s) 0.5-1.5 mm² (AWG 24...AWG 14) flexible without cable end control circuit: connector 2 cable(s) 0.2-1 mm² (AWG 24...AWG 14) solid without cable end
[Ui] Nazivna izolacijska trdnost690 V conforming to EN/IEC 60947-1 690 V conforming to CSA C22.2 No 14 690 V conforming to UL 508
Kompatibilnostna kodaLTMR
[Uimp] rated impulse withstand voltage4 kV supply, inputs and outputs conforming to EN/IEC 60947-4-1 6 kV current or voltage measurement circuit conforming to EN/IEC 60947-4-1 0.8 kV communication circuit conforming to EN/IEC 60947-4-1
Širina91 mm
Globina122.5 mm
tightening torquecontrol circuit: 0.5-0.6 N.m flat screwdriver 3 mm
protection typereverse polarity protection overload phase unbalance overload (long time) thermal protection power factor variation thermal overload protection locked rotor earth-leakage protection load fluctuation phase failure
contacts type and composition1 NO + 1 NC fault signal 3 NO
connection pitch5.08 mm
maximum operating rate1800 cyc/h
input current3.1 mA at 100 V 7.5 mA at 240 V
overvoltage categoryIII
electromagnetic compatibilityelectrostatic discharge, 3, 8 kV air, 6 kV contact, conforming to EN/IEC 61000-4-2 communication: surges (common mode), 2 kV, conforming to EN/IEC 61000-4-5 relay outputs and supply: surges (serial mode), 2 kV, conforming to EN/IEC 61000-4-5 relay outputs and supply: surges (common mode), 4 kV, conforming to EN/IEC 61000-4-5 control circuit: surges (common mode), 2 kV, conforming to EN/IEC 61000-4-5 radiated RF fields, 3, 10 V/m, conforming to EN/IEC 61000-4-3 fast transients immunity test (other circuits), level 3, 2 kV, conforming to EN/IEC 61000-4-4 fast transients immunity test (on supply and relay outputs), level 4, 4 kV, conforming to EN/IEC 61000-4-4 voltage dips and interruptions immunity test, 70 %, 500 ms, conforming to EN/IEC 61000-4-11 conducted RF disturbances, 10 V, conforming to EN/IEC 61000-4-6 temperature sensor: surges (serial mode), 0.5 kV, conforming to EN/IEC 61000-4-5 temperature sensor: surges (common mode), 1 kV, conforming to EN/IEC 61000-4-5 control circuit: surges (serial mode), 1 kV, conforming to EN/IEC 61000-4-5
measurement accuracy5...15 % earth fault current internal measurement 1 % voltage (100...830 V) 3 % power factor 5 % earth fault current external measurement +/- 30 min/year internal clock 0,02 temperature 5 % active and reactive power 0,02 current
pollution degree3
associated fuse rating4 A gG for output 0.5 A gG for control circuit
web servicesweb server
short-circuit withstand100 kA conforming to EN/IEC 60947-4-1
current state 1 guaranteedlogic input: 79...264 V and >= 2 mA for 25 ms
current state 0 guaranteedlogic input: 0...40 V and <= 15 mA for 25 ms
load current5 A at 250 V AC for logic output 5 A at 30 V DC for logic output
permissible power480 VA (AC-15), Ie = 2 A, 500000 cycles (output) 30 W (DC-13), Ie = 1.25 A, 500000 cycles (output)
network and machine diagnosis typewaiting time after overload tripping motor control command recording trip context information phase fault and earth fault trip counters starting current and time trip history information fault recording event recording remaining operating time before overload tripping running hours counter/operating time
logic input number6
maximum operating frequency2 Hz
metering typephase current I1, I2, I3 RMS temperature earth-fault current average current Iavg imbalance current
Okolje
Temperatura okoliškega zraka za delovanje-20-60 °C
IP stopnja zaščiteIP20
Temperatura okoliškega zraka za skladiščenje-40-80 °C
Nadmorska višina delovanja<= 2000 m without derating
Certifikati izdelkovC-Tick ABS UL DNV NOM RINA RMRoS BV LROS (Lloyds register of shipping) KERI EAC CCC CSA ATEX GL
StandardiCSA C22.2 No 14 EN 60947-4-1 IACS E10 UL 508 IEC 60947-4-1
Zaščitna obdelava12 x 24 hour cycles conforming to EN/IEC 60068-2-30 48 h conforming to EN/IEC 60070-2-11 TH conforming to EN/IEC 60068
fire resistance650 °C conforming to EN/IEC 60695-2-12 960 °C conforming to UL 94
mechanical robustnessvibrations mounted on symmetrical rail: 1 Gn, 5...300 Hz conforming to EN/IEC 60068-2-6 vibrations plate mounted: 4 Gn, 5...300 Hz conforming to EN/IEC 60068-2-6 shocks half sine wave acceleration: 15 Gn for 11 ms conforming to EN/IEC 60068-2-27