Opis

Pressure sensors XMLR 16bar - G 1/4 - 24VDC - 2xPNP - M12

Tehnične lastnosti

Glavno
Serija izdelkaOsiSense XM
Izdelek ali sestavni delelectronic pressure sensors
Kratko ime napraveXMLR
[Us] Nazivna napajalna npetost24 V DC SELV (voltage limits: 17-33 V)
pressure sensor typepressure transmitter
pressure switch type of operationpressure switch with 2 switching outputs
fluid connection typeG 1/4 (female) conforming to DIN 3852-Y
pressure sensor size232 psi 16 bar
controlled fluidfresh water (0-80 °C) air (-20-80 °C) hydraulic oil (-20-80 °C) refrigeration fluid (-20-80 °C)
maximum permissible accidental pressure6.2 MPa 900 psi 62 bar
destruction pressure900 psi 6.2 MPa 62 bar
Komplementarno
Višina93 mm
Teža izdelka0.19 kg
mechanical durability10000000 cycles
local signalling2 LEDs (yellow)light ON when switch is actuated:
[Uimp] rated impulse withstand voltage0.5 kV DC
Širina41 mm
Globina42 mm
Poraba toka<= 50 mA
protection typeovervoltage protection reverse polarity short-circuit protection overload protection
contacts type and composition2 NO/NC programmable
operating positionany position, but disposals can falsified the measurement in case of upside down mounting
electrical connectionmale connector M12, 4 pins
housing materialpolyacrylamide 316L stainless steel
maximum voltage drop2 V
repeat accuracy<= 0.2 % of the measuring range
adjustable range of switching point on falling pressure0.08-1.55 MPa 11.6-225 psi 0.8-15.5 bar
materials in contact with fluidceramic fluorocarbon FKM (Viton) 316L stainless steel
maximum delay first up300 ms
front materialpolyester
display accuracy<= 1 % of the measuring range
accuracy<= 1 % of the measuring range
type of output signaldiscrete
display response time typefast 50 ms normal 200 ms slow 600 ms
drift of the zero point+/- 0.1 % of measuring range/°C
time delay range0...50 s in steps of 1 second
electromagnetic compatibilitysusceptibility to electromagnetic fields: 10 V/m 80...2000 MHz conforming to EN/IEC 61000-4-3 immunity to conducted RF disturbances: 10 V 0.15...80 MHz conforming to EN/IEC 61000-4-6 surge immunity test: 1 kV conforming to EN/IEC 61000-4-5 electrical fast transient/burst immunity test: 2 kV conforming to EN/IEC 61000-4-4 electrostatic discharge immunity test: 8 kV air, 4 kV contact conforming to EN/IEC 61000-4-2
maximum switching current250 mA
controlled fluidair,hydraulic oil,fresh water,refrigeration fluid
minimum differential travel0.48 bar 48 kPa 7 psi
scale typefixed differential
measurement accuracy<= 0.6 % of the measuring range
adjustable range of switching point on rising pressure18.6-232 psi 1.28-16 bar 0.128-1.6 MPa
drift of the sensitivity+/- 0.03 % of measuring range/°C
display type4 digits 7 segments
temperature of controlled fluid-20-80 °C
response time on output<= 5 ms for discrete output
discrete output typesolid state PNP, 2 NO/NC programmable
Okolje
Temperatura okoliškega zraka za delovanje-20-80 °C
IP stopnja zaščiteIP65 conforming to EN/IEC 60529 IP67 conforming to EN/IEC 60529
Temperatura okoliškega zraka za skladiščenje-40-80 °C
Certifikati izdelkovcULus EAC
StandardiUL 61010-1 EN/IEC 61326-2-3
Odporno proti udarcu50 gn conforming to EN/IEC 60068-2-27
Odpornost proti vibracijam20 gn (f= 10-2000 Hz) conforming to EN/IEC 60068-2-6
markingCE