Menu
Vaša košarica

XPSMF3502 Schneider

XPSMF3502  Schneider
XPSMF3502 Schneider

Opis

Preventa safety PLC compact - 24 I not isolated

Tehnične lastnosti

Glavno
Serija izdelkaPreventa Safety automation
Izdelek ali sestavni delPreventa safety PLC compact
structure type10BASE-T/100BASE-TX, Modbus TCP/IP 10BASE-T/100BASE-TX, safe Ethernet
safety module nameXPSMF35
safety module applicationfor numerous machine safety functions and for the protection of personnel
safety use categorycategory 4 conforming to EN 954-1/ISO 13849-1 SIL 3 conforming to IEC 61508
Komplementarno
Višina113 mm
mounting support35 mm symmetrical DIN rail
Teža izdelka1.2 kg
Povezave - terminalianalogue input circuit: captive screw clamp terminals, 2 x 0.5 mm² (AWG 20) flexible with cable end power supply: captive screw clamp terminals, 1 x 0.25...1 x 2.5 mm² (AWG 22...AWG 16) flexible with cable end power supply: captive screw clamp terminals, 1 x 0.25...1 x 2.5 mm² (AWG 22...AWG 16) flexible without cable end discrete input/output circuit: captive screw clamp terminals, 2 x 0.14...2 x 0.5 mm² (AWG 28...AWG 20) solid without cable end discrete input/output circuit: captive screw clamp terminals, 2 x 0.14...2 x 0.75 mm² (AWG 28...AWG 18) flexible without cable end power supply: captive screw clamp terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 12) flexible without cable end discrete input/output circuit: captive screw clamp terminals, 2 x 0.25...2 x 0.34 mm² (AWG 22) flexible without cable end power supply: captive screw clamp terminals, 2 x 0.25...2 x 1 mm² (AWG 22...AWG 18) flexible without cable end power supply: captive screw clamp terminals, 2 x 0.5...2 x 1.5 mm² (AWG 22...AWG 16) flexible with cable end analogue input circuit: captive screw clamp terminals, 1 x 0.14...1 x 1.5 mm² (AWG 28...AWG 16) flexible without cable end counting inputs: captive screw clamp terminals, 1 x 0.14...1 x 1.5 mm² (AWG 28...AWG 16) flexible without cable end counting inputs: captive screw clamp terminals, 2 x 0.5 mm² (AWG 20) flexible with cable end analogue input circuit: captive screw clamp terminals, 1 x 0.14...1 x 1.5 mm² (AWG 28...AWG 16) solid without cable end counting inputs: captive screw clamp terminals, 1 x 0.14...1 x 1.5 mm² (AWG 28...AWG 16) solid without cable end analogue input circuit: captive screw clamp terminals, 1 x 0.25...1 x 0.5 mm² (AWG 22...AWG 20) flexible with cable end counting inputs: captive screw clamp terminals, 1 x 0.25...1 x 0.5 mm² (AWG 22...AWG 20) flexible with cable end analogue input circuit: captive screw clamp terminals, 1 x 0.25...1 x 1.5 mm² (AWG 22...AWG 16) flexible without cable end counting inputs: captive screw clamp terminals, 1 x 0.25...1 x 1.5 mm² (AWG 22...AWG 16) flexible without cable end analogue input circuit: captive screw clamp terminals, 2 x 0.14...2 x 0.5 mm² (AWG 28...AWG 20) solid without cable end counting inputs: captive screw clamp terminals, 2 x 0.14...2 x 0.5 mm² (AWG 28...AWG 20) solid without cable end analogue input circuit: captive screw clamp terminals, 2 x 0.14...2 x 0.75 mm² (AWG 28...AWG 18) flexible without cable end counting inputs: captive screw clamp terminals, 2 x 0.14...2 x 0.75 mm² (AWG 28...AWG 18) flexible without cable end discrete input/output circuit: captive screw clamp terminals, 2 x 0.5 mm² (AWG 20) flexible with cable end power supply: captive screw clamp terminals, 2 x 0.2...1 x 1.5 mm² (AWG 24...AWG 12) solid without cable end analogue input circuit: captive screw clamp terminals, 2 x 0.25...2 x 0.34 mm² (AWG 22) flexible without cable end counting inputs: captive screw clamp terminals, 2 x 0.25...2 x 0.34 mm² (AWG 22) flexible without cable end discrete input/output circuit: captive screw clamp terminals, 1 x 0.14...1 x 1.5 mm² (AWG 28...AWG 16) flexible without cable end discrete input/output circuit: captive screw clamp terminals, 1 x 0.14...1 x 1.5 mm² (AWG 28...AWG 16) solid without cable end power supply: captive screw clamp terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 12) flexible without cable end power supply: captive screw clamp terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 12) solid without cable end discrete input/output circuit: captive screw clamp terminals, 1 x 0.25...1 x 0.5 mm² (AWG 22...AWG 20) flexible with cable end discrete input/output circuit: captive screw clamp terminals, 1 x 0.25...1 x 1.5 mm² (AWG 22...AWG 16) flexible without cable end
wire stripping length9 mm
Širina253 mm
Globina66.5 mm
tightening torque0.22-0.25 N.m
[Us] rated supply voltage24 V DC - 15...20 %
Poraba toka9 A at 24 V DC on power supply
protection typeinternal fuse
voltage state 0 guaranteed<= 5 V for discrete input
voltage state 1 guaranteed24...30 V for discrete input
number of terminal blocks1 for counting inputs 1 for power supply 2 for discrete output 4 for analogue input circuit 5 for discrete input
response timedepending on size of application
analogue output typenot isolated
analogue input number8
discrete output number8
communication port protocolModbus TCP/IP with 4 RJ45 port(s), transmission rate: 100 Mbps, 10 Mbps, medium: dual twisted pair cable, category 5D or better safe Ethernet with 4 RJ45 port(s), transmission rate: 100 Mbps, 10 Mbps, medium: dual twisted pair cable, category 5D or better Modbus RTU with 1 SUB-D 9-pin female port(s), RS485, medium: shielded dual twisted pair cable Profibus with 1 SUB-D 9-pin female port(s), RS485, medium: shielded dual twisted pair cable
method of accessslave Modbus slave Modbus TCP/IP slave Profibus
discrete input number24 not isolated discrete input(s)
number of addresses122-122 for Modbus
exchange modehalf duplex, full duplex, autonegotiation Modbus TCP/IP half duplex, full duplex, autonegotiation safe Ethernet
discrete output current1 A at 60 °C (channels 4 and 8) 2 A at 50 °C (channels 4 and 8) 0.5 A at 60 °C (channels 1 to 3 and 5 to 7) <= 7 mA (all channels)
minimum load2 mA per discrete output
maximum leakage current1 mA, at 2 V at state 0 for discrete output
web serverclass A10, Modbus TCP/IP
web servicesModbus identification request, Modbus TCP/IP Modbus TCP/IP messaging (reading/writing of data words), Modbus TCP/IP Modbus TCP/IP server, Modbus TCP/IP Standard 502, Modbus TCP/IP
discrete input voltage20 V
discrete input current100 mA
current state 1 guaranteed3.5...4.5 mA (discrete input)
output voltage tolerance+/- 2 %
discrete output voltage24 V DC
current state 0 guaranteed1...1.5 mA (discrete input)
input protection typeprotected against short-circuit protected against short-circuit to earth
memory descriptionuser logic 250 kB application user logic 250 kB data
dV/dt1 V/µs counting inputs
input current limits0.4-23 mA 500 Ohm analogue input circuit
input voltage limits0.1...11.5 V analogue input circuit
clockwith, supplied by backup capacitor for 1 week following loss of supply
analogue input range0...20 mA with 500 Ohm shunt 0...10 V
overload protectionshutdown of outputs concerned with cyclic reconnection
operating distance<= 500 m (between station) shielded dual twisted pair cable counting inputs <= 100 m (between station) discrete input <= 100 m (between station) discrete output <= 300 m (between station) analogue input circuit
analogue input resolution12 bits
counting frequency100 kHz
counting input number2
counter inputs resolution24 bits
counting input typenon isolated
input overvoltage protection500-500 V for discrete input conforming to IEC 61000-4-5 -4-15 V for analogue input circuit
no load current0.75 A
function of moduleclosed circuit scanning of input channels for analogue input circuit measuring 0 to 20 mA currents using shunt for analogue input circuit monitoring safety actuators for discrete output monitoring safety detection for discrete input monitoring safety dialogue for discrete input monitoring safety dialogue for discrete output single-pole measuring of 0 to 10 V voltages for analogue input circuit
operating threshold0...0.05 V, 5 V low for counting inputs 13...33 V, 24 V high for counting inputs -3...5 V, 24 V low for counting inputs 4...6 V, 5 V high for counting inputs
conceptTransparent Ready, Modbus TCP/IP
external resistance250 Ohm for analogue input circuit 500 Ohm for analogue input circuit
maximum internal input resistance500 MOhm for signal source for analogue input circuit 1 kOhm for analogue input circuit 3.7 Ohm for counting inputs
safety accuracy+/- 2 % for analogue input circuit
Okolje
Temperatura okoliškega zraka za delovanje0-60 °C conforming to EN 61131-2
IP stopnja zaščiteIP20 (enclosure)
Stopnja onesnaženosti2
Temperatura okoliškega zraka za skladiščenje-40-85 °C conforming to EN 61131-2
relative humidity95-95 % supply not connected
Nadmorska višina delovanja< 2000 m
Odpornost na elektromagnetna polja10 V/m 26-1000 MHz conforming to EN/IEC 61000-4-3
StandardiIEC 61131 DIN V 19250 EN 50156 pending DIN V 0801
Odporno proti udarcu15 gn for 11 ms conforming to EN 61131-2
Odpornost proti vibracijam1 gn conforming to EN 61131-2 (f = 10-150 Hz)
Odpornost na elektrostatično razelektritev4 kV contact conforming to EN/IEC 61000-4-2 8 kV on air conforming to EN/IEC 61000-4-2
electrical shock protection classclass II conforming to EN/IEC 61131-2
Elektromagnetna kompatibilnostEN/IEC 61131-2
immunity to microbreaks10 ms