Menu
Vaša košarica

XPSMF4020 Schneider

XPSMF4020  Schneider
XPSMF4020 Schneider

Opis

Preventa safety PLC compact - Safe Ethernet, Modbus RTU

Tehnične lastnosti

Glavno
Serija izdelkaPreventa Safety automation
Izdelek ali sestavni delPreventa safety PLC compact
structure type10BASE-T/100BASE-TX, safe Ethernet
safety module nameXPSMF40
safety module applicationf use with numerous machine safety functions and for the protection of personel
safety use categorycategory 4 maximum conforming to EN 954-1 performance level e conforming to EN/ISO 13849-1 SIL 3 conforming to EN/IEC 61508
Komplementarno
Višina151.5 mm
mounting support35 mm symmetrical DIN rail
Teža izdelka1 kg
Povezave - terminalidiscrete input/output circuit: captive spring terminals, 1 x 0.5 mm² (AWG 20) flexible with cable end line control outputs: captive screw clamp terminals, 1 x 0.25...1 x 0.5 mm² (AWG 23...AWG 20) flexible with cable end discrete input/output circuit: captive screw clamp terminals, 1 x 0.25...1 x 1.5 mm² (AWG 23...AWG 15) flexible without cable end line control outputs: captive screw clamp terminals, 1 x 0.25...1 x 1.5 mm² (AWG 23...AWG 15) flexible without cable end power supply: captive screw clamp terminals, 1 x 0.25...1 x 2.5 mm² (AWG 23...AWG 14) flexible with cable end power supply: captive screw clamp terminals, 1 x 0.25...1 x 2.5 mm² (AWG 23...AWG 14) flexible without cable end discrete input/output circuit: captive spring terminals, 1 x 0.14...1 x 1.5 mm² (AWG 26...AWG 16) solid without cable end line control outputs: captive spring terminals, 1 x 0.14...1 x 1.5 mm² (AWG 26...AWG 16) solid without cable end discrete input/output circuit: captive spring terminals, 1 x 0.14...1 x 1.5 mm² (AWG 26...AWG 17) flexible without cable end line control outputs: captive spring terminals, 1 x 0.14...1 x 1.5 mm² (AWG 26...AWG 17) flexible without cable end power supply: captive spring terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 12) flexible without cable end line control outputs: captive spring terminals, 1 x 0.5 mm² (AWG 20) flexible with cable end power supply: captive spring terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 12) solid without cable end discrete input/output circuit: captive spring terminals, 1 x 0.25...1 x 0.34 mm² (AWG 22) flexible without cable end line control outputs: captive spring terminals, 1 x 0.25...1 x 0.34 mm² (AWG 22) flexible without cable end power supply: captive spring terminals, 1 x 0.25...1 x 2.5 mm² (AWG 23...AWG 12) flexible with cable end power supply: captive spring terminals, 1 x 0.25...1 x 2.5 mm² (AWG 23...AWG 12) flexible without cable end discrete input/output circuit: captive screw clamp terminals, 1 x 0.14...1 x 1.5 mm² (AWG 25...AWG 15) solid without cable end line control outputs: captive screw clamp terminals, 1 x 0.14...1 x 1.5 mm² (AWG 25...AWG 15) solid without cable end discrete input/output circuit: captive screw clamp terminals, 1 x 0.14...1 x 1.5 mm² (AWG 28...AWG 16) flexible without cable end line control outputs: captive screw clamp terminals, 1 x 0.14...1 x 1.5 mm² (AWG 28...AWG 16) flexible without cable end power supply: captive screw clamp terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 12) flexible without cable end power supply: captive screw clamp terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 12) solid without cable end discrete input/output circuit: captive screw clamp terminals, 1 x 0.25...1 x 0.5 mm² (AWG 23...AWG 20) flexible with cable end
wire stripping length10 mm for power supply captive screw clamp terminals 9 mm for discrete input/output circuit captive screw clamp terminals 9 mm for discrete input/output circuit captive spring terminals 9 mm for line control outputs captive screw clamp terminals 9 mm for line control outputs captive spring terminals 9 mm for power supply captive spring terminals
Širina74 mm
Globina153 mm
tightening torquediscrete input/output circuit: 0.22-0.25 N.m - on captive screw clamp terminals line control outputs: 0.22-0.25 N.m - on captive screw clamp terminals power supply: 0.5-0.5 N.m - on captive screw clamp terminals
[Us] rated supply voltage24 V DC - 15...20 %
Poraba toka8 A at 24 V DC on power supply
protection type10 A internal fuse
output voltage20 V line control outputs
voltage state 0 guaranteed<= 24 V for discrete input
voltage state 1 guaranteed24...30 V for discrete input
number of terminal blocks1 for power supply 2 for line control outputs 6 for discrete input/output circuit 8 for line control outputs
response timedepending on size of application
communication port protocolsafe Ethernet with 2 RJ45 port(s), transmission rate: 100 Mbps, 10 Mbps, medium: dual twisted pair cable, category 5D or better Modbus RTU with 1 RJ45 port(s), RS485, medium: shielded dual twisted pair cable
method of accessslave V0 Modbus serial
number of addresses122-122 for Modbus RTU
supplySELV or PELV conforming to EN/IEC 60950
exchange modehalf duplex, full duplex, autonegotiation safe Ethernet
discrete output current1 A at 60 °C (channels 4, 8, 12, 16, 20 and 24) 2 A at 50 °C (channels 4, 8, 12, 16, 20 and 24) 0.5 A at 60 °C (channels 1 to 3, 5 to 7, 9 to 11,13 to 15, 17 to 19, 21 to 23) <= 7 A (all channels)
minimum load2 mA per discrete output
maximum leakage current1 mA, at 2 V at state 0 for discrete output
discrete input voltage20 V
discrete input current100 mA
current state 1 guaranteed3.5...4.5 mA (discrete input)
output voltage tolerance+/- 2 %
discrete output voltage24 V DC
nominal output current60 mA for line control outputs
current state 0 guaranteed<= 1.5 mA (discrete input)
memory descriptionuser logic 250 kB application user logic 250 kB data
clockwith, supplied by backup capacitor for 1 week following loss of supply
overload protectionshutdown of outputs concerned with cyclic reconnection
operating distance<= 300 m between station for discrete input <= 300 m between station for discrete output
group of channels2 groups of 4 line control outputs
discrete I/O number24 configurable
input overvoltage protection-10-35 V for discrete input
no load current0.5 A
maximum discrete output number24 for not isolated
maximum input resistance7 kOhm
maximum discrete input number24 not isolated discrete input(s)
function of modulemonitoring safety actuators for discrete output monitoring safety detection for discrete input monitoring safety dialogue for discrete input monitoring safety dialogue for discrete output monitoring short-circuit and line break for line control outputs
Okolje
Temperatura okoliškega zraka za delovanje0-60 °C conforming to EN 61131-2
IP stopnja zaščiteIP20 (enclosure)
Stopnja onesnaženosti2
Temperatura okoliškega zraka za skladiščenje-40-85 °C conforming to EN 61131-2
relative humidity95-95 % supply not connected
Nadmorska višina delovanja< 2000 m
Odpornost na elektromagnetna polja10 V/m (80-2000 MHz), amplitude modulation 80 % conforming to EN/IEC 61000-4-3
StandardiEN 12067-2 : 2004 EN/IEC 61131-2 : 2003 EN 50156-1 : 2004 NFPA 72 : 2002 EN 54-2 : 1997 EN 61000-6-2 : 2001 NFPA 85 : 2001 IEC 61511 part 1-3 : 2004 EN 61000-6-4 : 2001 EN 298 : 2003 EN 230 : 1990 DIN VDE 0116 : 1989
Odporno proti udarcu15 gn for 11 ms conforming to EN 61131-2
Odpornost proti vibracijam1 gn conforming to EN 61131-2 (f = 9-150 Hz)
Odpornost na elektrostatično razelektritev4 kV contact conforming to EN/IEC 61000-4-2 8 kV on air conforming to EN/IEC 61000-4-2
electrical shock protection classclass II conforming to IEC 61131-2
Elektromagnetna kompatibilnostEN/IEC 61131-2
immunity to microbreaks10 ms