Control unit, TeSys U, 1.25-5A, 1P/3P motor protection & diagnostic with LCD display, class 5-30, coil 24V DC
Tehnične lastnosti
| Glavno | |
| Serija izdelka | TeSys U |
| Izdelek ali sestavni del | multifunction control unit |
| product name | TeSys U |
| utilisation category | AC-41 AC-44 AC-43 |
| Skupina izdelkov | TeSys |
| Aplikacija naprave | motor control motor protection |
| Kratko ime naprave | LUCM |
| network frequency | 40...60 Hz |
| [Uc] Krmilna napetost | 24 V DC |
| Združljivost izdelkov | power base LUB12 power base LUB32 power base LUB38 power base LUB120 power base LUB320 power base LUB380 reversing contactor breaker LU2B12BL reversing contactor breaker LU2B32BL reversing contactor breaker LU2B38BL |
| product specific application | most sophisticated control and protection requirements, with display |
| [Ue] rated operational voltage | 690 V AC |
| motor power kW | 1.5 kW at 400...440 V AC 50/60 Hz for 3 phases motors 2.2 kW at 500 V AC 50/60 Hz for 3 phases motors 3 kW at 690 V AC 50/60 Hz for 3 phases motors 0.55 kW at 400...440 V AC 50/60 Hz for 1 phase motors |
| load type | 3-phase motor - cooling: self-cooled - setting factory setting 3-phase motor - cooling: self-cooled, force cooled - setting settable single-phase motor - cooling: self-cooled, force cooled - setting settable |
| thermal protection adjustment range | 1.25-5 A |
| thermal overload class | class 5…30 - frequency limit: 50-60 Hz - temperature compensation: -25-55 °C conforming to IEC 60947-6-2 class 5…30 - frequency limit: 50-60 Hz - temperature compensation: -25-55 °C conforming to UL 508 |
| function available | protection function alarm earth fault protection protection against phase failure and phase imbalance manual or automatic reset log function protection against overload and short-circuit differentiation of thermal overload and magnetic fault overload, no-load running monitoring function, indication of main motor parameters |
| tripping threshold | 14.2 x Ir +/- 20 % |
| Komplementarno | |
| Višina | 66 mm |
| Teža izdelka | 0.175 kg |
| [Ui] Nazivna izolacijska trdnost | 690 V conforming to IEC 60947-6-2 600 V conforming to UL 60947-4-1 600 V conforming to CSA C22.2 No 60947-4-1 |
| Kompatibilnostna koda | LUCM |
| Širina | 45 mm |
| Globina | 60 mm |
| product certifications | CE UL CSA CCC EAC ASEFA ATEX Marine |
| standards | EN 60947-6-2 IEC 60947-6-2 UL 60947-4-1, with phase barrier CSA C22.2 No 60947-4-1, with phase barrier |
| Način pritrjevanja | plug-in (front face) |
| physical interface | RS485 multidrop - connector(s): RJ45 - location: front panel - communication protocol: Modbus RTU 19200 bit/s |
| Omejitve napetosti regulacijskega vezja | 20...28 V for DC circuit 24 V in operation 14.5 V for DC circuit 24 V drop-out |
| heat dissipation | 1.7-1.7 W for control circuit with LUB12 1.8-1.8 W for control circuit with LUB32 1.8-1.8 W for control circuit with LUB38 0.8-0.8 W for external auxiliary circuit |
| reset | automatic reset - setting: setting range manual - setting: factory setting manual - setting: setting range remote reset - setting: setting range |
| operating time | 35 ms opening with LUB12 for control circuit 35 ms opening with LUB32 for control circuit 35 ms opening with LUB38 for control circuit 75 ms closing with LUB12 for control circuit 65 ms closing with LUB32 for control circuit 65 ms closing with LUB38 for control circuit |
| typical current consumption | 150 mA at 24 V DC I maximum while closing with LUB12 200 mA at 24 V DC I maximum while closing with LUB32 200 mA at 24 V DC I maximum while closing with LUB38 70 mA at 24 V DC I rms sealed with LUB12 75 mA at 24 V DC I rms sealed with LUB32 75 mA at 24 V DC I rms sealed with LUB38 |
| safe separation of circuit | 400 V SELV between the control and auxiliary circuits conforming to IEC 60947-1 400 V SELV between the control or auxiliary circuit and the main circuit conforming to IEC 60947-1 |
| messages display capacity | 2 lines of 12 characters - display LCD - English - accuracy +/- 5 % - resolution 1 % of Ir 2 lines of 12 characters - display LCD - French - accuracy +/- 5 % - resolution 1 % of Ir 2 lines of 12 characters - display LCD - German - accuracy +/- 5 % - resolution 1 % of Ir 2 lines of 12 characters - display LCD - Italian - accuracy +/- 5 % - resolution 1 % of Ir 2 lines of 12 characters - display LCD - Spanish - accuracy +/- 5 % - resolution 1 % of Ir |
| information displayed | average current (factory setting) average current (settable) cause of last 5 faults (settable) current in phase (settable) earth leakage current (settable) phase imbalance (settable) thermal state of motor (settable) |
| time before reset | 1-1000 s - reset manual or automatic reset - setting settable 120-120 s - reset manual - setting factory setting |
| return time | <= 200 ms |
| Jezik | English - setting factory setting English, French, German, Italian, Spanish - setting settable |
| Okolje | |
| Temperatura okoliškega zraka za delovanje | -25-60 °C |
| IP stopnja zaščite | IP20 front panel and wired terminals conforming to IEC 60947-1 IP20 other faces conforming to IEC 60947-1 IP40 front panel outside connection zone conforming to IEC 60947-1 |
| Temperatura okoliškega zraka za skladiščenje | -40-85 °C |
| Nadmorska višina delovanja | 2000 m |
| Odporno proti udarcu | 10 gn power poles open conforming to IEC 60068-2-27 15 gn power poles closed conforming to IEC 60068-2-27 |
| Odpornost proti vibracijam | 2 gn, 5-300 Hz, power poles open conforming to IEC 60068-2-6 4 gn, 5-300 Hz, power poles closed conforming to IEC 60068-2-6 |
| Odpornost na elektrostatično razelektritev | 8 kV level 3 in open air conforming to IEC 61000-4-2 8 kV level 4 on contact conforming to IEC 61000-4-2 |
| Zaščitna obdelava | TH conforming to IEC 60068 |
| Odpornost proti hitrim prehodnim pojavom | 2 kV class 3 serial link conforming to IEC 61000-4-4 4 kV class 4 all circuits except for serial link conforming to IEC 61000-4-4 |
| fire resistance | 960 °C parts supporting live components conforming to IEC 60695-2-12 650 °C conforming to IEC 60695-2-12 |
| resistance to radiated fields | 10 V/m 3 conforming to IEC 61000-4-3 |
| immunity to microbreaks | 3 ms |
| immunity to voltage dips | 70 % / 500 ms conforming to IEC 61000-4-11 |
| immunity to radioelectric fields | 10 V conforming to IEC 61000-4-6 |