LU2MB0ES Schneider Electric

LU2MB0ES Schneider Electric
Opis
Reverser block for vertical mounting, TeSys U, 32A/690V, coil 48-72V AC/DC
Tehnične lastnosti
| Glavno | |
| Serija izdelka | TeSys U |
| Izdelek ali sestavni del | reverser block |
| Skupina izdelkov | TeSys |
| Aplikacija naprave | motor control |
| Kratko ime naprave | LU2MB |
| [Ie] rated operational current | 32 A |
| [Uc] Krmilna napetost | 48 V AC 50/60 Hz 48...72 V DC |
| device mounting | direct mounting |
| current consumption | 2300 mA at 48 V AC I maximum while closing 2300 mA at 48...72 V DC I maximum while closing |
| Komplementarno | |
| network frequency | 40...60 Hz |
| Višina | 80 mm |
| Teža izdelka | 0.4 kg |
| Povezave - terminali | control circuit: screw clamp terminals 1 cable(s) 0.34-1.5 mm² (external diameter: 3 mm) flexible with cable end control circuit: screw clamp terminals 1 cable(s) 0.75-1.5 mm² (external diameter: 3 mm) flexible without cable end control circuit: screw clamp terminals 1 cable(s) 0.75-1.5 mm² (external diameter: 3 mm) rigid control circuit: screw clamp terminals 2 cable(s) 0.34-1.5 mm² (external diameter: 3 mm) flexible with cable end control circuit: screw clamp terminals 2 cable(s) 0.75-1.5 mm² (external diameter: 3 mm) flexible without cable end control circuit: screw clamp terminals 2 cable(s) 0.75-1.5 mm² (external diameter: 3 mm) rigid power circuit: screw clamp terminals 1 cable(s) 1-10 mm² (external diameter: 4 mm) rigid power circuit: screw clamp terminals 1 cable(s) 1-6 mm² (external diameter: 4 mm) flexible with cable end power circuit: screw clamp terminals 1 cable(s) 2.5-10 mm² (external diameter: 4 mm) flexible without cable end power circuit: screw clamp terminals 2 cable(s) 1-6 mm² (external diameter: 4 mm) flexible with cable end power circuit: screw clamp terminals 2 cable(s) 1-6 mm² (external diameter: 4 mm) rigid power circuit: screw clamp terminals 2 cable(s) 1.5-6 mm² (external diameter: 4 mm) flexible without cable end |
| [Ui] Nazivna izolacijska trdnost | 690 V conforming to IEC 60947-6-2 600 V conforming to UL 60947-4-1 600 V conforming to CSA C22.2 No 60947-4-1 |
| Kompatibilnostna koda | LU2MB |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947-6-2 |
| Širina | 45 mm |
| Globina | 105 mm |
| tightening torque | control circuit: 0.8-1.2 N.m flat screwdriver 5 mm control circuit: 0.8-1.2 N.m Philips No 2 screwdriver 5 mm power circuit: 1.9-2.5 N.m flat screwdriver 6 mm power circuit: 1.9-2.5 N.m Philips No 2 screwdriver 6 mm |
| [Ue] rated operational voltage | 690 V AC power circuit |
| product certifications | CE UL CSA CCC EAC ASEFA ATEX Marine |
| standards | EN 60947-6-2 IEC 60947-6-2 UL 60947-4-1, with phase barrier CSA C22.2 No 60947-4-1, with phase barrier |
| Način pritrjevanja | plug-in |
| operating time | 150 ms with change of direction 75 ms without change of direction |
| inrush restraint duration | 25 ms AC 15 ms DC |
| Okolje | |
| Temperatura okoliškega zraka za delovanje | -25-60 °C with LUCM -25-70 °C with LUCA, LUCB, LUCC, LUCD |
| IP stopnja zaščite | IP20 conforming to IEC 60947-1 (front panel and wired terminals) IP20 conforming to IEC 60947-1 (other faces) IP40 conforming to IEC 60947-1 (front panel outside connection zone) |
| Temperatura okoliškega zraka za skladiščenje | -40-85 °C |
| Nadmorska višina delovanja | 2000 m |
| Odporno proti udarcu | 10 gn power poles open conforming to IEC 60068-2-27 15 gn power poles closed conforming to IEC 60068-2-27 |
| Odpornost proti vibracijam | 2 gn (f= 5-300 Hz) power poles open conforming to IEC 60068-2-27 4 gn (f= 5-300 Hz) power poles closed conforming to IEC 60068-2-27 |
| Odpornost na elektrostatično razelektritev | 8 kV level 3, in open air conforming to IEC 61000-4-2 8 kV level 4, on contact conforming to IEC 61000-4-2 |
| Zaščitna obdelava | TH conforming to IEC 60068 |
| Odpornost proti hitrim prehodnim pojavom | 2 kV class 3 serial link conforming to IEC 61000-4-4 4 kV class 4 all circuits except for serial link conforming to IEC 61000-4-4 |
| fire resistance | 960 °C parts supporting live components conforming to IEC 60695-2-12 650 °C conforming to IEC 60695-2-12 |
| resistance to radiated fields | 10 V/m level 3 conforming to IEC 61000-4-3 |
| non-dissipating shock wave | 1 kV serial mode conforming to IEC 60947-6-2 2 kV common mode conforming to IEC 60947-6-2 |
| immunity to radioelectric fields | 10 V conforming to IEC 61000-4-6 |