Menu
Vaša košarica

LC7K09015M7 Schneider Electric

LC7K09015M7  Schneider Electric
LC7K09015M7 Schneider Electric

Opis

TeSys K contactor - 3P - AC-3 = 440 V 9 A - 1 NC aux. - 220...230 V AC coil

Tehnične lastnosti

Glavno
Serija izdelkaTeSys K
Izdelek ali sestavni delcontactor
product nameTeSys K
Skupina izdelkovTeSys
Aplikacija napravecontrol
Kratko ime napraveLC7K
contactor applicationresistive load motor control
Komplementarno
Višina58 mm
mounting supportprinted circuit boards
Teža izdelka0.225 kg
Povezave - terminalisolder pins - busbar cross section: 1.5 x 0.9 mm
[Ui] Nazivna izolacijska trdnostpower circuit: 600 V conforming to UL 508 power circuit: 690 V conforming to IEC 60947-4-1 signalling circuit: 690 V conforming to IEC 60947-4-1 signalling circuit: 690 V conforming to IEC 60947-5-1 signalling circuit: 600 V conforming to UL 508 power circuit: 600 V conforming to CSA C22.2 No 14 signalling circuit: 600 V conforming to CSA C22.2 No 14
electrical durability0.18 Mcycles 20 A AC-1 at Ue <= 440 V 1.3 Mcycles 9 A AC-3 at Ue <= 440 V
mechanical durability10 Mcycles
Kompatibilnostna kodaLC7K
[Uimp] rated impulse withstand voltage8 kV
Širina45 mm
Globina57 mm
[Ue] rated operational voltagepower circuit: 690 V AC 50/60 Hz signalling circuit: <= 690 V AC 50/60 Hz
[Ith] conventional free air thermal current20 A (at 50 °C) for power circuit 10 A (at 50 °C) for signalling circuit
rated breaking capacity110 A at 415 V conforming to IEC 60947 110 A at 440 V conforming to IEC 60947 80 A at 500 V conforming to IEC 60947 110 A at 220...230 V conforming to IEC 60947 110 A at 380...400 V conforming to IEC 60947 70 A at 660...690 V conforming to IEC 60947
[Ie] rated operational current20 A (at <50 °C) at <= 440 V AC AC-1 for power circuit 9 A at <= 440 V AC AC-3 for power circuit 16 A (at <70 °C) at 690 V AC AC-1 for power circuit
[Uc] control circuit voltage220...230 V AC 50/60 Hz
[Icw] rated short-time withstand current90 A 50 °C - 1 s for power circuit 85 A 50 °C - 5 s for power circuit 80 A 50 °C - 10 s for power circuit 60 A 50 °C - 30 s for power circuit 45 A 50 °C - 1 min for power circuit 40 A 50 °C - 3 min for power circuit 20 A 50 °C - >= 15 min for power circuit 80 A - 1 s for signalling circuit 90 A - 500 ms for signalling circuit 110 A - 100 ms for signalling circuit
maximum operating rate3600 cyc/h
insulation resistance> 10 MOhm for signalling circuit
poles description3P
overvoltage categoryIII
minimum switching current5 mA for signalling circuit
Omejitve napetosti regulacijskega vezjaoperational: 0.85...1.1 Uc (at <50 °C) drop-out: 0.1...0.75 Uc (at <50 °C)
Inrush power in VA3-3 VA (at 20 °C)
Hold-in power consumption in VA3-3 VA (at 20 °C)
heat dissipation3-3 W
auxiliary contact composition1 NC
minimum switching voltage17 V for signalling circuit
signalling circuit frequency<= 400 Hz
auxiliary contacts type type instantaneous 1 NC
average impedance3 mOhm - Ith 20 A 50 Hz for power circuit
associated fuse rating25 A gG at <= 440 V for power circuit 25 A aM for power circuit 10 A gG for signalling circuit conforming to IEC 60947 10 A gG for signalling circuit conforming to VDE 0660
operating time30...40 ms coil energisation and NO closing 30 ms coil de-energisation and NO opening
motor power kW2.2 kW at 220...230 V AC 50/60 Hz AC-3 4 kW at 380...415 V AC 50/60 Hz AC-3 4 kW at 440 V AC 50/60 Hz AC-3 4 kW at 480 V AC 50/60 Hz AC-3 4 kW at 500...600 V AC 50/60 Hz AC-3 4 kW at 660...690 V AC 50/60 Hz AC-3 2.2 kW at 400 V AC 50/60 Hz AC-4
utilisation categoryAC-1 AC-4 AC-3
mechanical robustnessshocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
non overlap distance0.5 mm
control circuit typeAC at 50/60 Hz silent
safety reliability levelB10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Irms rated making capacity110 A AC for power circuit conforming to NF C 63-110 110 A AC for power circuit conforming to IEC 60947 110 A AC for signalling circuit conforming to IEC 60947
pole contact composition3 NO
Okolje
IP stopnja zaščiteIP2x conforming to VDE 0106
Temperatura okoliškega zraka za skladiščenje-50-80 °C
Nadmorska višina delovanja2000 m without
Certifikati izdelkovUL CSA
StandardiBS 5424 IEC 60947 NF C 63-110 VDE 0660
Zaščitna obdelavaTC conforming to IEC 60068 TC conforming to DIN 50016
flame retardanceV1 conforming to UL 94 requirement 2 conforming to NF F 16-101 requirement 2 conforming to NF F 16-102