Menu
Vaša košarica

LC1K09008P7 Schneider Electric

LC1K09008P7  Schneider Electric
LC1K09008P7 Schneider Electric

Opis

TeSys K contactor - 4P (2 NO + 2 NC) - AC-1 = 440 V 20 A - 230 V AC coil

Tehnične lastnosti

Glavno
Serija izdelkaTeSys K
Izdelek ali sestavni delcontactor
product nameTeSys K
Skupina izdelkovTeSys
Aplikacija napravecontrol
Kratko ime napraveLC1K
contactor applicationresistive load
Komplementarno
Višina58 mm
mounting supportrail plate
Teža izdelka0.18 kg
Povezave - terminaliscrew clamp terminals 1 cable(s) 1.5-4 mm²solid screw clamp terminals 1 cable(s) 0.75-4 mm²flexible without cable end screw clamp terminals 1 cable(s) 0.34-2.5 mm²flexible with cable end screw clamp terminals 2 cable(s) 1.5-4 mm²solid screw clamp terminals 2 cable(s) 0.75-4 mm²flexible without cable end screw clamp terminals 2 cable(s) 0.34-1.5 mm²flexible with cable end
[Ui] Nazivna izolacijska trdnostpower circuit: 600 V conforming to UL 508 power circuit: 690 V conforming to IEC 60947-4-1 power circuit: 600 V conforming to CSA C22.2 No 14
electrical durability0.18 Mcycles 20 A AC-1 at Ue <= 440 V
mechanical durability10 Mcycles
Kompatibilnostna kodaLC1K
[Uimp] rated impulse withstand voltage8 kV
Širina45 mm
Globina57 mm
tightening torque1.3 N.m - on screw clamp terminals - with screwdriver Philips No 2 1.3 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
[Ue] rated operational voltagepower circuit: 690 V AC 50/60 Hz
[Ith] conventional free air thermal current20 A (at 50 °C) for power circuit
rated breaking capacity110 A at 415 V conforming to IEC 60947 110 A at 440 V conforming to IEC 60947 80 A at 500 V conforming to IEC 60947 110 A at 220...230 V conforming to IEC 60947 110 A at 380...400 V conforming to IEC 60947 70 A at 660...690 V conforming to IEC 60947
[Uc] control circuit voltage230 V AC 50/60 Hz
maximum operating rate3600 cyc/h
poles description4P
overvoltage categoryIII
Omejitve napetosti regulacijskega vezjaoperational: 0.8...1.15 Uc (at <50 °C) drop-out: 0.2...0.75 Uc (at <50 °C)
Inrush power in VA30-30 VA (at 20 °C)
Hold-in power consumption in VA4.5-4.5 VA (at 20 °C)
heat dissipation1.3-1.3 W
signalling circuit frequency<= 400 Hz
average impedance3 mOhm - Ith 20 A 50 Hz for power circuit
associated fuse rating25 A gG at <= 440 V for power circuit 25 A aM for power circuit
operating time10...20 ms coil de-energisation and NO opening 10...20 ms coil energisation and NO closing 15...25 ms coil de-energisation and NC closing 5...15 ms coil energisation and NC opening
utilisation categoryAC-1
mechanical robustnessshocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
control circuit typeAC at 50/60 Hz
safety reliability levelB10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Irms rated making capacity110 A AC for power circuit conforming to NF C 63-110 110 A AC for power circuit conforming to IEC 60947
pole contact composition2 NO + 2 NC
Okolje
IP stopnja zaščiteIP2x conforming to VDE 0106
Temperatura okoliškega zraka za skladiščenje-50-80 °C
Nadmorska višina delovanja2000 m without
Certifikati izdelkovCSA UL
StandardiBS 5424 IEC 60947 NF C 63-110 VDE 0660
Zaščitna obdelavaTC conforming to IEC 60068 TC conforming to DIN 50016
flame retardanceV1 conforming to UL 94 requirement 2 conforming to NF F 16-101 requirement 2 conforming to NF F 16-102