Menu
Vaša košarica

ATV71HC40N4D Schneider

ATV71HC40N4D  Schneider
ATV71HC40N4D Schneider

Opis

variable speed drive ATV71 - 355kW-600HP - 480V - EMC filter-graphic terminal

Tehnične lastnosti

Glavno
Serija izdelkaAltivar 71
Izdelek ali sestavni delvariable speed drive
[Us] Nazivna napajalna npetost380...480 V - 15...10 %
variantreinforced version without DC choke
nominal output current671 A at 2.5 kHz 380 V 3 phases 355 kW 671 A at 2.5 kHz 460 V 3 phases 355 kW 759 A at 2.5 kHz 380 V 3 phases 400 kW / 600 hp 759 A at 2.5 kHz 460 V 3 phases 400 kW / 600 hp
product specific applicationcomplex, high-power machines
network number of phases3 phases
component nameATV71
line current512 A for 480 V 3 phases 355 kW 568 A for 480 V 3 phases 400 kW / 600 hp 637 A for 380 V 3 phases 355 kW 709 A for 380 V 3 phases 400 kW / 600 hp
maximum motor cable length100 m shielded cable 200 m unshielded cable
asynchronous motor control profilesensorless flux vector control (SFVC) (voltage or current vector) voltage/frequency ratio (2 or 5 points) ENA (Energy adaptation) system for unbalanced loads flux vector control (FVC) with sensor (current vector)
output frequency0.1-500 Hz
apparent power419.3 kVA at 380 V 3 phases 355 kW 466.6 kVA at 380 V 3 phases 400 kW / 600 hp
motor power kW355 kW, 3 phases at 380...480 V 400 kW, 3 phases at 380...480 V
switching frequency2.5...8 kHz adjustable 2.5...8 kHz with derating factor
maximum transient current1138 A for 60 s 3 phases 400 kW / 600 hp 1252 A for 2 s 3 phases 400 kW / 600 hp 1006 A for 60 s 3 phases 355 kW 1107 A for 2 s 3 phases 355 kW
assembly stylewith heat sink
nominal switching frequency2.5 kHz
EMC filterintegrated
type of polarizationno impedance for Modbus
motor power hp600 hp, 3 phases at 380...480 V
prospective line Isc50 kA for 3 phases
Komplementarno
network frequency47.5...63 Hz
Višina1390 mm
Teža izdelka225 kg
local signalling1 LED (red)drive voltage:
Širina890 mm
Globina377 mm
tightening torque0.6 N.m (AI1-/AI1+, AI2, AO1, R1A, R1B, R1C, R2A, R2B, LI1...LI6, PWR) 41 N.m, 360 lb.in (PC/-, PO, PA/+) 41 N.m, 360 lb.in (R/L1.1, S/L2.1, T/L3.1, R/L1.2, S/L2.2, T/L3.2) 41 N.m, 360 lb.in (U/T1, V/T2, W/T3)
Omejitve napajalne napetosti323-528 V
protection typeagainst exceeding limit speed: drive short-circuit between motor phases: drive thermal protection: drive motor phase break: motor power removal: motor thermal protection: motor against input phase loss: drive break on the control circuit: drive input phase breaks: drive line supply overvoltage: drive line supply undervoltage: drive overcurrent between output phases and earth: drive overheating protection: drive overvoltages on the DC bus: drive
operating positionvertical +/- 10 degree
output voltage<= power supply voltage
electrical connectionterminal, clamping capacity: 2.5 mm², AWG 14 (AI1-/AI1+, AI2, AO1, R1A, R1B, R1C, R2A, R2B, LI1...LI6, PWR) terminal, clamping capacity: 8 x 185 mm² (PC/-, PO, PA/+) terminal, clamping capacity: 2 x 2 x 185 mm² (R/L1.1, S/L2.1, T/L3.1, R/L1.2, S/L2.2, T/L3.2) terminal, clamping capacity: 4 x 185 mm² (U/T1, V/T2, W/T3)
OznačevanjeCE
transmission rate4800 bps, 9600 bps, 19200 bps, 38.4 Kbps for Modbus on terminal 9600 bps, 19200 bps for Modbus on front face 20 kbps, 50 kbps, 125 kbps, 250 kbps, 500 kbps, 1 Mbps for CANopen
type of cablewith a NEMA Type1 kit: 3 wire(s)UL 508 cable at 40 °C, copper 75 °C / PVC with an IP21 or an IP31 kit: 3 wire(s)IEC cable at 40 °C, copper 70 °C / PVC without mounting kit: 1 wire(s)IEC cable at 45 °C, copper 70 °C / PVC without mounting kit: 1 wire(s)IEC cable at 45 °C, copper 90 °C / XLPE/EPR
insulation resistance> 1 mOhm 500 V DC for 1 minute to earth
insulationelectrical between power and control
supply frequency50...60 Hz - 5...5 %
accuracy+/- 0.6 % (AI1-/Al1+) for a temperature variation 60 °C +/- 0.6 % (AI2) for a temperature variation 60 °C +/- 1 % (AO1) for a temperature variation 60 °C
maximum switching currentR1, R2: 2 A at 250 V AC inductive load, cos phi = 0.4 R1, R2: 2 A at 30 V DC inductive load, cos phi = 0.4 R1, R2: 5 A at 250 V AC resistive load, cos phi = 1 R1, R2: 5 A at 30 V DC resistive load, cos phi = 1
discrete output typeconfigurable relay logic: (R1A, R1B, R1C) NO/NC - 100000 cycles configurable relay logic: (R2A, R2B) NO - 100000 cycles
response time <= 100 ms in STO (Safe Torque Off) AO1 2 ms, tolerance +/- 0.5 ms for analog output(s) R1A, R1B, R1C 7 ms, tolerance +/- 0.5 ms for discrete output(s) R2A, R2B 7 ms, tolerance +/- 0.5 ms for discrete output(s)
discrete input logicnegative logic (sink) (LI1...LI5), > 16 V (state 0), < 10 V (state 1) positive logic (source) (LI1...LI5), < 5 V (state 0), > 11 V (state 1) negative logic (sink) (LI6)if configured as logic input, > 16 V (state 0), < 10 V (state 1) positive logic (source) (LI6)if configured as logic input, < 5 V (state 0), > 11 V (state 1)
product destinationsynchronous motors asynchronous motors
acceleration and deceleration rampslinear adjustable separately from 0.01 to 9000 s S, U or customized automatic adaptation of ramp if braking capacity exceeded, by using resistor
analogue output typeAO1 software-configurable logic output 10 V 20-20 mA AO1 software-configurable current 0...20 mA, impedance: 500 Ohm, resolution 10 bits AO1 software-configurable voltage 0...10 V DC, impedance: 470 Ohm, resolution 10 bits
physical interface2-wire RS 485 for Modbus
transient overtorque170-170 % of nominal motor torque +/- 10 % for 60 s every 10 minutes 220-220 % of nominal motor torque +/- 10 % for 2 s
torque accuracy+/- 15 % in open-loop mode, without speed feedback +/- 5 % in closed-loop mode with encoder feedback
data format8 bits, 1 stop, even parity for Modbus on front face 8 bits, odd even or no configurable parity for Modbus on terminal
frequency resolutionanalog input: 0.024/50 Hz display unit: 0.1 Hz
connector type1 RJ45 (on front face) for Modbus 1 RJ45 (on terminal) for Modbus male SUB-D 9 on RJ45 for CANopen
analogue input number2
motor slip compensationnot available in voltage/frequency ratio (2 or 5 points) automatic whatever the load suppressable adjustable
discrete output number2
communication port protocolCANopen Modbus
regulation loopadjustable PI regulator
transmission frameRTU for Modbus
analogue output number1
minimum switching current3 mA at 24 V DC for configurable relay logic
method of accessslave CANopen
speed range1-100 for asynchronous motor in open-loop mode, without speed feedback 1-1000 for asynchronous motor in closed-loop mode with encoder feedback 1-50 for synchronous motor in open-loop mode, without speed feedback
discrete input number7
linearity error+/- 0.15 % of maximum value (AI1-/Al1+, AI2) +/- 0.2 % (AO1)
number of addresses1-127 for CANopen 1-247 for Modbus
braking to standstillby DC injection
discrete input typeLI1...LI5: programmable 24 V DC with level 1 PLC, impedance: 3500 Ohm LI6: switch-configurable 24 V DC with level 1 PLC, impedance: 3500 Ohm LI6: switch-configurable PTC probe 0-6 , impedance: 1500 Ohm PWR: safety input 24 V DC, impedance: 1500 Ohm conforming to ISO 13849-1 level d
analogue input typeAI1-/Al1+ bipolar differential voltage: +/- 10 V DC 24 V max, resolution 11 bits + sign AI2 software-configurable current: 0...20 mA, impedance: 242 Ohm, resolution 11 bits AI2 software-configurable voltage: 0...10 V DC 24 V max, impedance: 30000 Ohm, resolution 11 bits
supplyinternal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10 mA, protection type: overload and short-circuit protection internal supply: 24 V DC (21-27 V), <200 mA, protection type: overload and short-circuit protection
braking torque<= 150 % with braking or hoist resistor 30 % without braking resistor
speed accuracy+/- 0.01 % of nominal speed in closed-loop mode with encoder feedback 0.2 Tn to Tn +/- 10 % of nominal slip without speed feedback 0.2 Tn to Tn
sampling duration2 ms +/- 0.5 ms (AI1-/Al1+) - analog input(s) 2 ms +/- 0.5 ms (Al2) - analog input(s) 2 ms +/- 0.5 ms (LI1...LI5) - discrete input(s) 2 ms +/- 0.5 ms (LI6)if configured as logic input - discrete input(s)
synchronous motor control profilevector control without speed feedback
option cardcommunication card for CC-Link communication card for Modbus TCP communication card for Modbus/Uni-Telway overhead crane card communication card for Profibus DP communication card for Profibus DP V1 controller inside programmable card communication card for DeviceNet communication card for Ethernet/IP communication card for Fipio I/O extension card communication card for Interbus-S interface card for encoder communication card for Modbus Plus
Okolje
Temperatura okoliškega zraka za delovanje-10-50 °C (without)
IP stopnja zaščiteIP41 on upper part conforming to EN/IEC 60529 IP30 on the front panel conforming to EN/IEC 61800-5-1 IP41 on upper part conforming to EN/IEC 61800-5-1 IP54 on lower part conforming to EN/IEC 60529 IP54 on lower part conforming to EN/IEC 61800-5-1 IP00 conforming to EN/IEC 60529 IP00 conforming to EN/IEC 61800-5-1 IP30 on side parts conforming to EN/IEC 60529 IP30 on side parts conforming to EN/IEC 61800-5-1 IP30 on the front panel conforming to EN/IEC 60529
Stopnja onesnaženosti2 conforming to EN/IEC 61800-5-1 3 conforming to UL 840
Temperatura okoliškega zraka za skladiščenje-25-70 °C
relative humidity5-95 % without condensation conforming to IEC 60068-2-3 5-95 % without dripping water conforming to IEC 60068-2-3
Nadmorska višina delovanja<= 1000 m without 1000...3000 m with current derating 1 % per 100 m
Certifikati izdelkovNOM 117 GOST CSA C-Tick UL
StandardiEN/IEC 61800-3 IEC 60721-3-3 class 3C2 EN 55011 class A group 2 EN 61800-3 environments 1 category C3 EN 61800-3 environments 2 category C3 UL Type 1 EN/IEC 61800-5-1
Odporno proti udarcu4 gn for 11 ms conforming to EN/IEC 60068-2-27
Odpornost proti vibracijam0.6 gn (f= 10-200 Hz) conforming to EN/IEC 60068-2-6 1.5 mm peak to peak (f= 3-10 Hz) conforming to EN/IEC 60068-2-6
Elektromagnetna kompatibilnost1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6 electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 voltage dips and interruptions immunity test conforming to IEC 61000-4-11
dielectric strength3535 V DC between earth and power terminals 5092 V DC between control and power terminals
noise level77 dB conforming to 86/188/EEC