enclosed variable speed drive ATV31 - 1.1kW - 240V - IP55

Tehnične lastnosti

Glavno
Serija izdelkaAltivar 31
Izdelek ali sestavni delvariable speed drive
[Us] Nazivna napajalna npetost200...240 V - 15...10 %
product destinationasynchronous motors
nominal output current6.9 A 4 kHz
IP degree of protectionIP55
product specific applicationsimple machine
network number of phasessingle phase
component nameATV31
line current10.2 A 240 V 1 kA 12.1 A 200 V 1 kA
asynchronous motor control profilefactory set : constant torque sensorless flux vector control with PWM type motor control signal
apparent power2.4 kVA
motor power kW1.1 kW
maximum transient current10.4 A for 60 s
assembly styleenclosed
EMC filterintegrated
motor power hp1.5 hp
prospective line Isc1 kA
supply frequency50...60 Hz - 5...5 %
power dissipation in W74 W at nominal load
speed range1-50
transient overtorque150-170 % of nominal motor torque
analogue input number3
Komplementarno
Teža izdelka8.8 kg
local signalling1 LED (red)drive voltage: four 7-segment display unitsCANopen bus status:
tightening torqueAl1, Al2, Al3, AOV, AOC, R1A, R1B, R1C, R2A, R2B, LI1...LI6: 0.6-0.6 N.m L1, L2, L3, U, V, W, PA, PB, PA/+, PC/-: 0.8-0.8 N.m
Omejitve napajalne napetosti170-264 V
protection typeinput phase breaks: drive line supply overvoltage and undervoltage safety circuits: drive line supply phase loss safety function, for three phases supply: drive motor phase breaks: drive overcurrent between output phases and earth (on power up only): drive overheating protection: drive short-circuit between motor phases: drive thermal protection: motor
operating positionvertical +/- 10 degree
output voltage<= power supply voltage
electrical connectionAl1, Al2, Al3, AOV, AOC, R1A, R1B, R1C, R2A, R2B, LI1...LI6 terminal 2.5-2.5 mm² AWG 14 L1, L2, L3, U, V, W, PA, PB, PA/+, PC/- terminal 2.5-2.5 mm² AWG 14
OznačevanjeCE
transmission rate10, 20, 50, 125, 250, 500 kbps or 1 Mbps for CANopen via VW3 CANTAP2 adaptor 4800, 9600 or 19200 bps for Modbus
switching frequency2...16 kHz adjustable
insulation resistance>= 500 mOhm 500 V DC for 1 minute
insulationelectrical between power and control
maximum switching current2 A at 250 V AC on inductive load - cos phi = 0.4 - L/R = 7 ms (R1-R2) 2 A at 30 V DC on inductive load - cos phi = 0.4 - L/R = 7 ms (R1-R2) 5 A at 250 V AC on resistive load - cos phi = 1 - L/R = 0 ms (R1-R2) 5 A at 30 V DC on resistive load - cos phi = 1 - L/R = 0 ms (R1-R2)
discrete output typeconfigurable relay logic: (R1A, R1B, R1C) 1 NO + 1 NC - 100000 cycles configurable relay logic: (R2A, R2B) NC - 100000 cycles
response timeAOV, AOC 8 ms for analog R1A, R1B, R1C, R2A, R2B 8 ms for discrete
discrete input logicpositive logic (source) (LI1...LI6), < 5 V (state 0), > 11 V (state 1) logic input not wired (LI1...LI4), < 13 V (state 1) negative logic (source) (LI1...LI6), > 19 V (state 0)
acceleration and deceleration rampslinear adjustable separately from 0.1 to 999.9 s S, U or customized
analogue output typeAOC configurable current: 0...20 mA, impedance: 800 Ohm, resolution: 8 bits AOV configurable voltage: 0...10 V, impedance: 470 Ohm, resolution: 8 bits
physical interfaceRS485 multidrop serial link for Modbus
frequency resolutiondisplay unit: 0.1 Hz analog input: 0.1...100 Hz
connector type1 RJ45 for CANopen via VW3 CANTAP2 adaptor 1 RJ45 for Modbus
motor slip compensationautomatic whatever the load adjustable suppressable
discrete output number2
communication port protocolCANopen Modbus
regulation loopfrequency PI regulator
transmission frameRTU for Modbus
analogue output number2
minimum switching current10 mA 5 V DC R1-R2
discrete input number6
linearity error+/- 0.2 % for output
number of addresses1-127 for CANopen via VW3 CANTAP2 adaptor 1-247 for Modbus
braking to standstillby DC injection
discrete input type(LI1...LI6) programmable at 24 V, 0-100 mA for PLC, impedance: 3500 Ohm
analogue input typeAI3 configurable current 0...20 mA, impedance: 250 Ohm AI1 configurable voltage 0...10 V, input voltage 30 V max, impedance: 30000 Ohm AI2 configurable voltage +/- 10 V, input voltage 30 V max, impedance: 30000 Ohm
supplyinternal supply for logic inputs 19-30 V, <100 mA overload protection internal supply for logic inputs 19-30 V, <100 mA short-circuit protection internal supply for reference potentiometer 10-10.8 V, <10 mA overload protection internal supply for reference potentiometer 10-10.8 V, <10 mA short-circuit protection
braking torque<= 150 % during 60 s with braking resistor 100 % with braking resistor continuously 50 % without braking resistor
sampling durationLI1...LI6: 4 ms discrete AI1, AI2, AI3: 8 ms analog
speed drive output frequency0.5-500 Hz
nominal switching frequency4 kHz
time constant5 ms for reference change
network frequency limits47.5-63 Hz
number of drive127 for CANopen via VW3 CANTAP2 adaptor 31 for Modbus
Okolje
Temperatura okoliškega zraka za delovanje-10-50 °C without (with protective cover on top of the drive) -10-60 °C with derating factor (without protective cover on top of the drive)
Stopnja onesnaženosti2
Temperatura okoliškega zraka za skladiščenje-25-70 °C
relative humidity5-95 % without condensation conforming to IEC 60068-2-3 5-95 % without dripping water conforming to IEC 60068-2-3
Nadmorska višina delovanja<= 1000 m without >= 1000 m with current derating 1 % per 100 m
Certifikati izdelkovCSA N998 C-Tick UL
StandardiEN 50178
Odporno proti udarcu15 gn for 11 ms conforming to EN/IEC 60068-2-27
Odpornost proti vibracijam1 gn (f= 13-150 Hz) conforming to EN/IEC 60068-2-6 1.5 mm (f= 3-13 Hz) conforming to EN/IEC 60068-2-6
Zaščitna obdelavaTC
Elektromagnetna kompatibilnost1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3
dielectric strength2040 V DC between earth and power terminals 2880 V AC between control and power terminals