ATV12PU15M3 Schneider Electric

ATV12PU15M3 Schneider Electric
Opis
variable speed drive ATV12 - 1.5kW - 2hp - 200..240V - 3ph - on base plate
Tehnične lastnosti
| Glavno | |
| Serija izdelka | Altivar 12 |
| Izdelek ali sestavni del | variable speed drive |
| [Us] Nazivna napajalna npetost | 200...240 V - 15...10 % |
| product destination | asynchronous motors |
| IP degree of protection | IP20 without blanking plate on upper part |
| product specific application | simple machine |
| Količina na set/komplet | set of 1 |
| network number of phases | 3 phases |
| component name | ATV12 |
| line current | 11.1 A at 200 V 9.3 A at 240 V |
| asynchronous motor control profile | voltage/frequency ratio (V/f) sensorless flux vector control quadratic voltage/frequency ratio |
| motor power kW | 1.5 kW |
| assembly style | on base plate |
| EMC filter | without EMC filter |
| motor power hp | 2 hp |
| communication port protocol | Modbus |
| speed range | 1-20 |
| noise level | 0 dB |
| transient overtorque | 150-170 % of nominal motor torque depending on drive rating and type of motor |
| built-in fan | without |
| Komplementarno | |
| Višina | 143 mm |
| Teža izdelka | 1 kg |
| Širina | 105 mm |
| Globina | 98.2 mm |
| tightening torque | 1.2 N.m |
| protection type | line supply overvoltage line supply undervoltage overcurrent between output phases and earth overheating protection short-circuit between motor phases against input phase loss in three-phase thermal motor protection via the drive by continuous calculation of I²t |
| operating position | vertical +/- 10 degree |
| output voltage | 200...240 V 3 phases |
| electrical connection | terminal, clamping capacity: 5.5 mm², AWG 10 (L1, L2, L3, U, V, W, PA, PC) |
| Označevanje | CE |
| transmission rate | 4800 bit/s 9600 bit/s 19200 bit/s 38400 bit/s |
| switching frequency | 2...16 kHz adjustable 4...16 kHz with derating factor |
| insulation | electrical between power and control |
| supply frequency | 50/60 Hz +/- 5 % |
| maximum switching current | 2 A 250 V AC inductive cos phi = 0.4 L/R = 7 ms logic relay 2 A 30 V DC inductive cos phi = 0.4 L/R = 7 ms logic relay 3 A 250 V AC resistive cos phi = 1 L/R = 0 ms logic relay 4 A 30 V DC resistive cos phi = 1 L/R = 0 ms logic relay |
| discrete output type | logic output LO+, LO- protected relay output R1A, R1B, R1C 1 C/O |
| discrete input logic | negative logic (sink), > 16 V (state 0), < 10 V (state 1), input impedance 3.5 kOhm positive logic (source), 0...< 5 V (state 0), > 11 V (state 1) |
| acceleration and deceleration ramps | U S linear from 0 to 999.9 s |
| analogue output type | AO1 software-configurable voltage: 0...10 V, impedance: 470 Ohm, resolution 8 bits AO1 software-configurable current: 0...20 mA, impedance: 800 Ohm, resolution 8 bits |
| physical interface | 2-wire RS 485 for Modbus |
| frequency resolution | analog input: converter A/D, 10 bits display unit: 0.1 Hz |
| connector type | 1 RJ45 (on front face) for Modbus |
| analogue input number | 1 |
| motor slip compensation | adjustable preset in factory |
| discrete output number | 2 |
| transmission frame | RTU for Modbus |
| analogue output number | 1 |
| minimum switching current | 5 mA at 24 V DC for logic relay |
| discrete input number | 4 |
| linearity error | +/- 0.3 % of maximum value for analogue input |
| number of addresses | 1-247 for Modbus |
| braking to standstill | by DC injection, <30 s |
| discrete input type | programmable LI1...LI4 24 V 18...30 V |
| analogue input type | configurable current AI1 0...20 mA 250 Ohm configurable voltage AI1 0...10 V 30 kOhm configurable voltage AI1 0...5 V 30 kOhm |
| supply | internal supply for reference potentiometer: 5 V DC (4.75-5.25 V), <10 mA, protection type: overload and short-circuit protection internal supply for logic inputs: 24 V DC (20.4-28.8 V), <100 mA, protection type: overload and short-circuit protection |
| braking torque | up to 70 % of nominal motor torque without braking resistor |
| sampling duration | 20 ms, tolerance +/- 1 ms for logic input 10 ms for analogue input |
| prospective line Isc | 5 kA |
| power range | 1.1-2 kW at 200-240 V 3 phases |
| speed drive output frequency | 0.5-400 Hz |
| communication service | read holding registers (03) 29 words write single register (06) 29 words write multiple registers (16) 27 words read/write multiple registers (23) 4/4 words read device identification (43) |
| maximum transient current | 11.2 A for 60 s |
| motor starter type | variable speed drive |
| continuous output current | 7.5 A at 4 kHz |
| nominal switching frequency | 4 kHz |
| time constant | 20 ms +/- 1 ms for reference change |
| Okolje | |
| Temperatura okoliškega zraka za delovanje | -10-40 °C protective cover from the top of the drive removed 40-60 °C with current derating 2.2 % per °C |
| Temperatura okoliškega zraka za skladiščenje | -25-70 °C |
| relative humidity | 5-95 % without condensation conforming to IEC 60068-2-3 5-95 % without dripping water conforming to IEC 60068-2-3 |
| Nadmorska višina delovanja | <= 1000 m without > 1000...3000 m with current derating 1 % per 100 m |
| Certifikati izdelkov | UL C-Tick CSA GOST NOM |
| Odporno proti udarcu | 15 gn conforming to EN/IEC 60068-2-27 for 11 ms |
| Odpornost proti vibracijam | 1 gn (f = 13-200 Hz) conforming to EN/IEC 60068-2-6 1.5 mm peak to peak (f = 3-13 Hz) - drive unmounted on symmetrical DIN rail - conforming to EN/IEC 60068-2-6 |
| Elektromagnetne emisije | radiated emissions environment 1 category C2 conforming to EN/IEC 61800-3 2...16 kHz shielded motor cable conducted emissions with additional EMC filter environment 1 category C1 conforming to EN/IEC 61800-3 4...12 kHz shielded motor cable <5 m conducted emissions with additional EMC filter environment 1 category C2 conforming to EN/IEC 61800-3 4...12 kHz shielded motor cable <20 m conducted emissions with additional EMC filter environment 2 category C3 conforming to EN/IEC 61800-3 4...12 kHz shielded motor cable <20 m |
| Elektromagnetna kompatibilnost | electrical fast transient/burst immunity test level 4 conforming to EN/IEC 61000-4-4 electrostatic discharge immunity test level 3 conforming to EN/IEC 61000-4-2 immunity to conducted disturbances level 3 conforming to EN/IEC 61000-4-6 radiated radio-frequency electromagnetic field immunity test level 3 conforming to EN/IEC 61000-4-3 surge immunity test level 3 conforming to EN/IEC 61000-4-5 voltage dips and interruptions immunity test conforming to EN/IEC 61000-4-11 |