TeSys GS - switch-disconnector-fuse - 3 P - 63A - DIN 00C

Tehnične lastnosti

Glavno
network typeDC AC
Izdelek ali sestavni delswitch-disconnector-fuse
product nameTeSys GS
Skupina izdelkovTeSys
Opis polov3P
Kratko ime napraveGS2G
network frequency50/60 Hz
protected poles description3t
[Ie] rated operational current40 A at 440 V 2 poles in series per phase DC-23A 40 A at 440 V 2 poles in series per phase DC-23B 63 A at 400 V AC-23A 63 A at 400 V AC-23B 63 A at 500 V AC-23A 63 A at 500 V AC-23B 63 A at 690 V AC-23A 63 A at 690 V AC-23B
contacts type and composition3 NO
fuse size000
fuse typeDIN
[Ith] conventional free air thermal current63 A (at 40 °C)
Komplementarno
mounting supportplate
Povezave - terminalipower circuit: lugs-ring terminals10-25 mm²
[Ui] Nazivna izolacijska trdnost750 V AC 50/60 Hz
electrical durability1500 cycles AC-23A 1500 cycles DC-23A 300 cycles AC-23B 300 cycles DC-23B
mechanical durability10000 cycles
Kompatibilnostna kodaGS2G
tightening torquepower circuit: 3.2-3.2 N.m
[Icm] rated short-circuit making capacity100 kA at 400 V with protection by gG fuses
breaking capacity500 A at 400 V (AC-23B)
type of operating handleexternal right side external frontal
making capacity630 A at 400 V AC-23B
short-circuit withstand10.6 kA
rated operational power in W30 kW at 400 V 40 kW at 500 V 55 kW at 690 V
Okolje
Temperatura okoliškega zraka za delovanje-20-70 °C
IP stopnja zaščiteIP20 conforming to IEC 60529 (with terminal cover)
Temperatura okoliškega zraka za skladiščenje-40-80 °C
Certifikati izdelkovCE
StandardiIEC 60947-3
fire resistance850 °C fuse cover conforming to IEC 60695-2-1 960 °C body conforming to IEC 60695-2-1
Višina118 mm
net weight1 kg
Širina136 mm