Menu
Vaša košarica

ATV950D11N4E Schneider Electric

ATV950D11N4E  Schneider Electric
ATV950D11N4E Schneider Electric

Opis

variable speed drive, ATV950, 11kW, 400/480V, w braking unit/switch, IP55

Tehnične lastnosti

Glavno
Serija izdelkaAltivar Process ATV900
Izdelek ali sestavni delvariable speed drive
Aplikacija napraveindustrial application
Kratko ime napraveATV950
[Us] Nazivna napajalna npetost380...480 V - 15...10 %
product destinationsynchronous motors asynchronous motors
variantwith braking chopper with load break switch
IP degree of protectionIP55 conforming to IEC 61800-5-1 IP55 conforming to IEC 60529
network number of phases3 phases
line current19.8 A at 380 V (normal duty) 17 A at 480 V (normal duty) 14.1 A at 380 V (heavy duty) 12.5 A at 480 V (heavy duty)
asynchronous motor control profilevariable torque standard constant torque standard optimized torque mode
apparent power14.1 kVA at 480 V (normal duty) 10.4 kVA at 480 V (heavy duty)
motor power kW11 kW (normal duty) 7.5 kW (heavy duty)
switching frequency2...16 kHz adjustable 4...16 kHz with derating factor
maximum transient current28.2 A during 60 s (normal duty) 24.8 A during 60 s (heavy duty)
nominal switching frequency4 kHz
EMC filterintegrated with 50 m conforming to EN/IEC 61800-3 category C2 integrated with 150 m conforming to EN/IEC 61800-3 category C3
motor power hp15 hp normal duty 10 hp heavy duty
prospective line Isc50 kA
speed drive output frequency0.1-599 Hz
communication port protocolModbus serial Ethernet/IP Modbus TCP
discrete input logic16 preset speeds
type of coolingforced convection
continuous output current23.5 A at 4 kHz for normal duty 16.5 A at 4 kHz for heavy duty
safety functionSTO (safe torque off) SIL 3
option cardslot A: communication module for Profibus DP V1 slot A: communication module for Profinet slot A: communication module for DeviceNet slot A: communication module for EtherCAT slot A: communication module for CANopen daisy chain RJ45 slot A: communication module for CANopen SUB-D 9 slot A: communication module for CANopen screw terminals slot A/slot B/slot C: digital and analog I/O extension module slot A/slot B/slot C: output relay extension module slot B: 5/12 V digital encoder interface module slot B: analog encoder interface module slot B: resolver encoder interface module communication module for Ethernet Powerlink
supply frequency50...60 Hz +/- 5 %
synchronous motor control profilepermanent magnet motor synchronous reluctance motor
Komplementarno
Višina678 mm
Teža izdelka13.7 kg
mounting modewall mount
local signallinglocal diagnostic: 3 LED (mono/dual colour) embedded communication status: 5 LED (dual colour) communication module status: 2 LED (dual colour) presence of voltage: 1 LED (red)
Širina264 mm
Globina330 mm
protection typethermal protection: motor safe torque off: motor motor phase break: motor thermal protection: drive safe torque off: drive overheating: drive overcurrent between output phases and earth: drive overload of output voltage: drive short-circuit protection: drive motor phase break: drive overvoltages on the DC bus: drive line supply overvoltage: drive line supply undervoltage: drive line supply phase loss: drive overspeed: drive break on the control circuit: drive
output voltage<= power supply voltage
electrical connectioncontrol: screw terminal0.5...1.5 mm² line side: screw terminal6 mm² motor: screw terminal6...10 mm² DC bus: screw terminal6...10 mm²
transmission rate10/100 Mbit/s for Ethernet IP/Modbus TCP 4.8, 9.6, 19.2, 38.4 kbit/s for Modbus serial
accuracy+/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input +/- 1 % AQ1, AQ2 for a temperature variation 60 °C analog output
maximum switching currentrelay output R1 on resistive load, cos phi = 1 : 3 A at 250 V AC relay output R1 on resistive load, cos phi = 1 : 3 A at 30 V DC relay output R1 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 250 V AC relay output R1 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 30 V DC relay output R2, R3 on resistive load, cos phi = 1 : 5 A at 250 V AC relay output R2, R3 on resistive load, cos phi = 1 : 5 A at 30 V DC relay output R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 250 V AC relay output R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 30 V DC
discrete output typelogic output DQ+ 0-1 kHz <= 30 V DC 100 mA programmable as pulse output DQ+ 0-30 kHz <= 30 V DC 20 mA logic output DQ- 0-1 kHz <= 30 V DC 100 mA
discrete input logicpositive logic (source) (DI1...DI8), < 5 V (state 0), > 11 V (state 1) negative logic (sink) (DI1...DI8), > 16 V (state 0), < 10 V (state 1) positive logic (source) (DI7, DI8), < 0.6 V (state 0), > 2.5 V (state 1) positive logic (source) (STOA, STOB), < 5 V (state 0), > 11 V (state 1)
acceleration and deceleration rampslinear adjustable separately from 0.01...9999 s
analogue output typesoftware-configurable voltage AQ1, AQ2: 0...10 V DC impedance 470 Ohm, resolution 10 bits software-configurable current AQ1, AQ2: 0...20 mA impedance 500 Ohm, resolution 10 bits
physical interface2-wire RS 485 for Modbus serial
data format8 bits, configurable odd, even or no parity for Modbus serial
frequency resolutiondisplay unit: 0.1 Hz analog input: 0.012/50 Hz
connector type2 RJ45 for Ethernet IP/Modbus TCP on the control block 1 RJ45 for Modbus serial on the control block
analogue input number3
motor slip compensationadjustable automatic whatever the load not available in permanent magnet motor law can be suppressed
discrete output number2
transmission frameRTU for Modbus serial
analogue output number2
minimum switching currentrelay output R1, R2, R3: 5 mA at 24 V DC
method of accessslave Modbus TCP
discrete input number10
linearity errorAI1, AI2, AI3: +/- 0.15 % of maximum value for analog input AQ1, AQ2: +/- 0.2 % for analog output
number of addresses1-247 for Modbus serial
braking to standstillby DC injection
discrete input typeDI1...DI8 programmable, 24 V DC (<= 30 V), impedance: 3.5 kOhm DI7, DI8 programmable as pulse input: 0-30 kHz, 24 V DC (<= 30 V) STOA, STOB safe torque off, 24 V DC (<= 30 V), impedance: > 2.2 kOhm
analogue input typeAI1, AI2, AI3 software-configurable voltage: 0...10 V DC, impedance: 30 kOhm, resolution 12 bits AI1, AI2, AI3 software-configurable current: 0...20 mA/4...20 mA, impedance: 250 Ohm, resolution 12 bits
supplyexternal supply for digital inputs: 24 V DC (19-30 V), <1.25 mA, protection type: overload and short-circuit protection internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10 mA, protection type: overload and short-circuit protection internal supply for digital inputs and STO: 24 V DC (21-27 V), <200 mA, protection type: overload and short-circuit protection
sampling duration2 ms +/- 0.5 ms (DI1...DI8) - discrete input 5 ms +/- 1 ms (DI7, DI8) - pulse input 1 ms +/- 1 ms (AI1, AI2, AI3) - analog input 5 ms +/- 1 ms (AQ1, AQ2) - analog output
exchange modehalf duplex, full duplex, autonegotiation Ethernet IP/Modbus TCP
relay output number3
IP degree of protectionIP55
relay output typeconfigurable relay logic R1: fault relay NO/NC electrical durability 100000 cycles configurable relay logic R2: sequence relay NO electrical durability 1000000 cycles configurable relay logic R3: sequence relay NO electrical durability 1000000 cycles
input compatibilityDI1...DI8: discrete input level 1 PLC conforming to EN/IEC 61131-2 DI7, DI8: pulse input level 1 PLC conforming to IEC 65A-68 STOA, STOB: discrete input level 1 PLC conforming to EN/IEC 61131-2
refresh timerelay output (R1, R2, R3): 5 ms (+/- 0.5 ms)
isolationbetween power and control terminals
type of polarizationno impedance for Modbus serial
Okolje
Temperatura okoliškega zraka za delovanje-15-40 °C (without) 40-50 °C (with derating factor)
Stopnja onesnaženosti2 conforming to EN/IEC 61800-5-1
Temperatura okoliškega zraka za skladiščenje-40-70 °C
relative humidity5-95 % without condensation conforming to IEC 60068-2-3
Nadmorska višina delovanja<= 1000 m without 1000...4800 m with current derating 1 % per 100 m
Certifikati izdelkovTÜV REACH
Standardi EN/IEC 61800-3 environment 1 category C2 EN/IEC 61800-3 environment 2 category C3 EN/IEC 61800-3 EN/IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1
Odporno proti udarcu15 gn for 11 ms conforming to IEC 60068-2-27
Odpornost proti vibracijam1.5 mm peak to peak (f= 2-13 Hz) conforming to IEC 60068-2-6 1 gn (f= 13-200 Hz) conforming to IEC 60068-2-6
Elektromagnetna kompatibilnostelectrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
environmental characteristicchemical pollution resistance class 3C3 conforming to EN/IEC 60721-3-3 dust pollution resistance class 3S3 conforming to EN/IEC 60721-3-3
operating positionvertical +/- 10 degree
markingCE
noise level52 dB conforming to 86/188/EEC
insulation resistance> 1 MOhm 500 V DC for 1 minute to earth
maximum THDI <48 % from 80...100 % of load conforming to IEC 61000-3-12