Menu
Vaša košarica

56515 Schneider Electric

56515  Schneider Electric
56515 Schneider Electric

Opis

residual current protection relay, Vigirex RH197M, 30 mA to 30 A, 24VDC to 130VDC, 48 VAC 50/60Hz, alarm 50% or 100% IDn

Tehnične lastnosti

Glavno
Serija izdelkaVigirex
Izdelek ali sestavni delresidual current protection relay
Skupina izdelkovVigirex
Kratko ime napraveRH197M
Združljivost serije/obsega Vigirex RH TOA earth leakage current sensor Vigirex RH A earth leakage current sensor
relay applicationresidual current protection relay
Komplementarno
Višina98.7 mm
mounting supportDIN rail
Teža izdelka0.3 kg
Povezave - terminaliauxiliary power supply: terminal block cable(s) 0.2-2.5 mm² flexible AWG 24...AWG 12 sensor: terminal block cable(s) 0.2-2.5 mm² flexible AWG 24...AWG 12 sensor: terminal block cable(s) 0.2-2.5 mm² rigid AWG 24...AWG 12 sensor: terminal block cable(s) 0.25-2.5 mm² flexible AWG 24...AWG 12 voltage presence: terminal block cable(s) 0.2-2.5 mm² flexible AWG 24...AWG 12 voltage presence: terminal block cable(s) 0.2-2.5 mm² rigid AWG 24...AWG 12 voltage presence: terminal block cable(s) 0.25-2.5 mm² flexible AWG 24...AWG 12 auxiliary power supply: terminal block cable(s) 0.2-2.5 mm² rigid AWG 24...AWG 12 auxiliary power supply: terminal block cable(s) 0.25-2.5 mm² flexible AWG 24...AWG 12 fault: terminal block cable(s) 0.2-2.5 mm² flexible AWG 24...AWG 12 fault: terminal block cable(s) 0.2-2.5 mm² rigid AWG 24...AWG 12 fault: terminal block cable(s) 0.25-2.5 mm² flexible AWG 24...AWG 12 relay test and fault reset: terminal block cable(s) 0.2-2.5 mm² flexible AWG 24...AWG 12 relay test and fault reset: terminal block cable(s) 0.2-2.5 mm² rigid AWG 24...AWG 12 relay test and fault reset: terminal block cable(s) 0.25-2.5 mm² flexible AWG 24...AWG 12
wire stripping lengthauxiliary power supply: 7 mm fault: 7 mm relay test and fault reset: 7 mm sensor: 7 mm voltage presence: 7 mm
Kompatibilnostna kodaRH197M
Širina71.2 mm
Globina65.8 mm
tightening torqueauxiliary power supply: 0.6-0.6 N.m fault: 0.6-0.6 N.m relay test and fault reset: 0.6-0.6 N.m sensor: 0.6-0.6 N.m voltage presence: 0.6-0.6 N.m
[Us] rated supply voltage48 V AC 50/60 Hz 24...130 V DC
earth-leakage protection classclass A si class AC
residual earth-leakage time delay adjustment typeinstantaneous 0.03-0.03 A adjustable 7 settings 0.03-30 A 0-4.5 s
[Ithe] conventional enclosed thermal current8 A
power consumption in VA4 VA
overvoltage categoryIV
refresh time0.5 s
earthing systemTN-S TT IT
minimum load10 mA at 12 V
mechanical robustnessfire resistance conforming to IEC 60695-2-1 IK protection 2 joules: IK07 conforming to EN 50102 IP protection: IP20 conforming to IEC 60529 IP protection: IP30 conforming to IEC 60529 IP protection: IP40 conforming to IEC 60529 vibrations 13.2...100 Hz: 0.7 g vibrations 2...13.2 Hz: +/- 1 mm
type of measurementearth fault current internal measurement, range: - 7...7 %
test functionlocal remote test
signal contacts composition1 NO
tamperproof of settingsprotected by sealable cover
monitoringelectronics (watchdog) power supply (continuous) relay/sensor link (continuous)
Okolje
Temperatura okoliškega zraka za delovanje-25-55 °C
Temperatura okoliškega zraka za skladiščenje-40-85 °C
electrical shock protection classclass II
Elektromagnetna kompatibilnostconducted and radiated emissions: , B, conforming to CISPR 11 conducted radio-frequency immunity test: , 3, conforming to IEC 61000-4-6 electrostatic discharge immunity test: , 4, conforming to IEC 61000-4-2 high-energy conducted susceptibility: , 4, conforming to IEC 61000-4-5 low-energy conducted susceptibility: , 4, conforming to IEC 61000-4-4 radiated susceptibility: , 3, conforming to IEC 61000-4-3