Menu
Vaša košarica

METSEPM2120 Schneider Electric

METSEPM2120  Schneider Electric
METSEPM2120 Schneider Electric

Opis

EasyLogic PM2120, Power & Energy meter, up to 15th H, LED, RS485, class 1

Tehnične lastnosti

Glavno
Izdelek ali sestavni delpower meter
product nameEasyLogic PM2100
Skupina izdelkovEasyLogic
Kratko ime napravePM2120
Komplementarno
network frequency50 Hz 60 Hz
Višina96 mm
mounting supportframework
Teža izdelka300 g
Povezave - terminalicurrent transformer: screw connection (bottom) 6 voltage inputs: screw connection (top) 4
control type3 x button
mounting modeclip-on
Kompatibilnostna kodaPM2120
local signallingred LED: output signal 1...9999000 pulse/ k_h (kWh, kVAh, kVARh) green LED: module operation and integrated communication
Širina96 mm
Globina76.09 mm total: 61.64 mm embedded:
product certificationsCE conforming to IEC 61010-1 cULus conforming to UL 61010-1 cULus conforming to CSA C22.2 No 61010-1 RCM EAC C-Tick
Materialpolycarbonate
[Us] rated supply voltage44...277 V AC 45...65 Hz +/- 10 % 44...277 V DC +/- 10 %
[In] rated current1 A 5 A
number of outputs0
number of inputs0
mounting positionvertical
provided equipment1 x installation guide
function availablereal time clock
measurement accuracyapparent power +/- 1 % active energy +/- 1 % reactive energy +/- 1 % active power +/- 1 % voltage +/- 0.5 % power factor +/- 0.01 current +/- 0.5 % frequency +/- 0.05 %
display type7 segments LED
communication port protocolModbus RTU at 4800 bps, 9600 bps, 19200 bps, 38.4 Kbps even/odd or none - 2 wires, insulation 2500 V
analogue input typecurrent (impedance <= 0.3 mOhm) voltage (impedance > 5 MOhm)
refresh timeconfigurable from 1 to 60 min
Razred električne izolacijedouble insulation class II
maximum power consumption in W3.3 W (power lines (AC)) 2 W at 277 V (power lines (DC))
communication serviceremote monitoring
device applicationsub billing power monitoring
flame retardanceV-0 conforming to UL 94
type of measurementapparent power min/max, total active and reactive power min/max, total current min/max, avg voltage min/max, avg frequency min/max, avg total current harmonic distortion THD (I) per phase total voltage harmonic distortion THD (U) per phase power factor min/max, avg apparent energy total active and reactive energy total
communication port supportscrew terminal block: RS485
measurement voltage35-480 V AC 50/60 Hz between phases 20-277 V AC 50/60 Hz between phase and neutral 480-999000 V AC 50/60 Hz with external VT
sampling rate64 samples/cycle
maximum power consumption in VA6 VA at 277 V AC
metering typecurrent I, I1, I2, I3 peak demand power PM, QM, SM active, reactive, apparent energy (signed, four quadrant) peak demand currents active power P, P1, P2, P3 calculated neutral current voltage U, U21, U32, U13, V, V1, V2, V3 unbalance current reactive power Q, Q1, Q2, Q3 demand power P, Q, S apparent power S, S1, S2, S3
measurement current5-6000 mA
frequency measurement range45-65 Hz
data recordingtime stamping min/max for 8 parameters
accuracy classclass 1 active energy conforming to IEC 62053-21 class 1 reactive energy conforming to IEC 62053-24 class 5 harmonic distorsion (I THD & U THD)
messages display capacity3 fields of 4 characters
information displayeddemand current (past value) demand current (present value) demand power (past value) demand power (present value) voltage current frequency energy consumption harmonic distortion power factor active power apparent power reactive power unbalanced in %
tamperproof of settingsprotected by access code
display digits12 digit(s) - 14.2 mm in height
power quality analysis total harmonic distortion up to the 15th harmonic
cybersecurityenable/disable communication ports
display colourred
measurement categorycategory III 480-480 V category II 480-600 V
Okolje
Temperatura okoliškega zraka za delovanje-10-60 °C
IP stopnja zaščiteIP54 front: conforming to IEC 60529 IP30 body: conforming to IEC 60529
Stopnja onesnaženosti2
Temperatura okoliškega zraka za skladiščenje-25-70 °C
relative humidity5-95 % at 50-50 °C
overvoltage categoryIII
Nadmorska višina delovanja<= 2000 m
Elektromagnetna kompatibilnostelectrostatic discharge conforming to IEC 61000-4-2 radiated radio-frequency electromagnetic field immunity test conforming to IEC 61000-4-3 electrical fast transient/burst immunity test conforming to IEC 61000-4-4 surge immunity test conforming to IEC 61000-4-5 conducted RF disturbances conforming to IEC 61000-4-6 magnetic field at power frequency conforming to IEC 61000-4-8 voltage dips and interruptions immunity test conforming to IEC 61000-4-11 emission tests conforming to FCC part 15 class A
service life7 year(s)