LV847288 Schneider Electric

LV847288  Schneider Electric
LV847288 Schneider Electric

Opis

Micrologic 6.0 X control unit, for Masterpact MTZ circuit breakers, fixed, LSIG protections

Tehnične lastnosti

Glavno
network typeAC
Izdelek ali sestavni delcontrol unit
Skupina izdelkovMasterpact
Opis polov3P 4P
Aplikacija napraveequipment protection, monitoring and control
Kratko ime napraveMicrologic 6.0 X
trip unit technologyelectronic
trip unit nameMicrologic 6.0 X
trip unit rating1000-1000 A 5000-5000 A 2500-2500 A 3200-3200 A 630-630 A 1250-1250 A 400-400 A 4000-4000 A 800-800 A 6300-6300 A 1600-1600 A 2000-2000 A
protected poles description3P 3d 4P 3d 4P 4d 4P 3d + OSN 4P 3d + N/2
protection typeoverload protection (long time) conforming to ANSI 49 instantaneous short-circuit protection conforming to ANSI 50 short time short-circuit protection conforming to ANSI 51 earth fault conforming to ANSI 51N
Združljivost serije/obsega Masterpact MTZ1 circuit breaker Masterpact MTZ2 circuit breaker Masterpact MTZ3 circuit breaker
trip unit protection functionsLSIG
circuit breaker applicationdistribution IEC standard
Komplementarno
network frequency50/60 Hz
mounting modefixed
instantaneous pick-up adjustment range2...15 x In adjustable in step of 0.5 x In with embedded HMI 2...15 x In adjustable in step of 0.1 x In with Ecoreach software or Masterpact MTZ mobile app Ii enable on/off
long time delay adjustment typeadjustable in step of 0.5 s
instantaneous pick-up adjustment type Iiadjustable
long time pick-up adjustment range0.4...1 x In adjustable in step of 1 A
electromagnetic compatibilityelectrostatic discharge immunity test conforming to IEC 61000-4-2 susceptibility to electromagnetic fields conforming to IEC 61000-4-3 electrical fast transient/burst immunity test conforming to IEC 61000-4-4 1.2/50 µs shock waves immunity test conforming to IEC 61000-4-5 conducted RF disturbances conforming to IEC 61000-4-6 conducted and radiated emissions A conforming to CISPR 22
measurement accuracypower factor: +/- 1 % active energy Ep IN/OUT/tot: +/- 1 % - 10...10 GWh reactive energy Ep IN/OUT/tot: +/- 2 % - 10...10 GVARh apparent energy Es IN/OUT/tot: +/- 1 % - 10...10 GVAh unbalance current: +/- 0.5 % frequency: +/- 0.005 Hz voltage V21, V32, V13, VLLavg: +/- 0.5 % 208...690 x 1.2 V voltage V21, V32, V13, VLNavg: +/- 0.5 % 120...400 x 1.2 V apparent power S, S1, S2, S3, Sdemand: +/- 1 % active power P, P1, P2, P3, Pdemand: +/- 1 % reactive power Q, Q1, Q2, Q3, Qdemand: +/- 2 % current I1, I2, I3, Iavg, Idemand for MTZ1: +/- 0.5 % 40...1600 x 1.2 A current I1, I2, I3, Iavg, Idemand for MTZ2: +/- 0.5 % 40...4000 x 1.2 A current I1, I2, I3, Iavg, Idemand for MTZ3: +/- 0.5 % 80...6300 x 1.2 A
display typeLCD display - 128 x 96 pixels
communication port protocolBluetooth 4.0 LE peer to peer 30 kbit/s NFC peer to peer conforming to ISO 15963 USB peer to peer 115 kbauds
operating time0 ms in fast 20 ms in standard
thermal memoryyes
[tr] long-time delay adjustment range12.5-600 s at 1.5 x Ir 0.5-24 s at 6 x Ir 0.7-16.6 s at 7.2 x Ir
type of measurementpower meter
zone selective interlocking ZSIwith
short-time delay adjustment typeadjustable
[tsd] short-time delay adjustment range0.1-0.4 s I²t=on 0-0.4 s I²t=off
[Isd] short-time pick-up adjustment range1.5...10 x Ir adjustable in step of 0.5 x Ir with embedded HMI 1.5...10 x Ir adjustable in step of 0.1 x Ir with Ecoreach software or Masterpact MTZ mobile app
measurement voltage145.6-828 V AC 50/60 Hz per phase
[Ig] ground-fault pick-up adjustment range conforming to IEC with In > 400 A 0.2...1 x In adjustable in step of 10 A conforming to IEC with In <= 400 A 0.3...1 x In adjustable in step of 10 A Ig enable on/off
ground-fault time delay adjustment type -tgadjustable
ground-fault pick-up adjustment typeadjustable
network and machine diagnosis typesystem (HMI) health state overview: circuit breaker health state standard) contacts state: circuit breaker health state standard) micrologic service life: circuit breaker health state standard) tripping cause indication: circuit breaker tripping cause standard) identification card: diagnostic data standard) configured alarms synthesis: diagnostic data standard) monitored function: diagnostic data standard) operation: diagnostic data standard) micrologic test: test standard) protection test: test standard) selectivity test: test standard) trip context information: crisis management standard) operation: advanced diagnostic standard) breaker service life: circuit breaker health state standard)
metering typecurrent I1, I2, I3, In, Ig: maximum standard) average voltage Vavg standard) active power P, P1, P2, P3 standard) reactive power Q, Q1, Q2, Q3 standard) apparent power S, S1, S2, S3 standard) power factor standard) frequency standard) total current harmonic distortion THD (I): inst, avg, avg min, avg max fundamental voltage standard) total current harmonic distortion THD (I): inst, avg, avg min, avg max RMS voltage standard) voltage V21, V32, V13, V1, V2, V3: instantaneous standard) voltage V21, V32, V13, V1, V2, V3: minimum standard) voltage V21, V32, V13, V1, V2, V3: maximum standard) total voltage harmonic distortion THD (V): inst, avg, avg min, avg max fundamental voltage standard) total voltage harmonic distortion THD (V): inst, avg, avg min, avg max RMS voltage standard) demand current I1, I2, I3, In, Iavg standard) demand power P, Q, S standard)
frequency measurement range45-250 Hz
data recordingmaintenance logs data logs min/max of instantaneous values alarm logs event logs time stamping
energy managementmeasurement ,active, reactive and apparent energy (standard) measurement ,electrical network (standard) measurement ,energy (standard)
accuracy classclass 5: total current harmonic distortion THD (I) class 0.5: unbalance voltage class 1: active and reactive energy by pulse counting (+/- W.h, +/- VAR.h) class 2: total voltage harmonic distortion THD (V)
[tg] ground-fault time delay adjustment range0.1-0.4 s I²t=on 0-0.4 s I²t=off
Okolje
StandardiIEC 60092-202 EN/IEC 60255-1 EN/IEC 60947-2 EN/IEC 60947-1