Menu
Vaša košarica

LV432775 Schneider

LV432775  Schneider
LV432775 Schneider

Opis

circuit breaker Compact NSX400F, 36 kA at 415 VAC, Micrologic 2.3 M trip unit 320 A, 3 poles 3d

Tehnične lastnosti

Glavno
[In] rated current320 A at 65 °C
Serija izdelkaNSX400...630
network typeAC
breaking capacity codeF 36 kA 415 V AC
Izdelek ali sestavni delcircuit breaker
product nameCompact NSX
utilisation categorycategory A
Skupina izdelkovCompact
breaking capacity40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 85 kA at 240 V AC 50/60 Hz conforming to UL 508 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 480 V AC 50/60 Hz conforming to UL 508 20 kA at 600 V AC 50/60 Hz conforming to UL 508 20 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
suitability for isolationyes conforming to EN 60947-2 yes conforming to IEC 60947-2
Opis polov3P
Aplikacija napravemotor
Kratko ime napraveCompact NSX400F
trip unit technologyelectronic
network frequency50/60 Hz
[Ics] rated service breaking capacity40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
trip unit nameMicrologic 2.3 M
protected poles description3t
[Ue] rated operational voltage690 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage8 kV
[Ui] rated insulation voltage800 V AC 50/60 Hz
pollution degree3 conforming to IEC 60664-1
trip unit protection functionsLSoI
Komplementarno
Višina255 mm
mounting supportbackplate
Teža izdelka6.05 kg
control typetoggle
mounting modefixed
electrical durability12000 cycles 440 V In/2 conforming to IEC 60947-2 3000 cycles 690 V In conforming to IEC 60947-2 6000 cycles 440 V In conforming to IEC 60947-2 6000 cycles 690 V In/2 conforming to IEC 60947-2
mechanical durability15000 cycles
Kompatibilnostna kodaNSX400
local signallingLED 95 % Ith LED ready
Širina140 mm
Globina110 mm
long time pick-up adjustment type Iradjustable 9 settings
upside connectionfront
downside connectionfront
protection typeL : for overload protection (long time) So : for short time short-circuit protection with fixed delay I : for instantaneous short-circuit protection
connection pitch45 mm
instantaneous pick-up adjustment range4800 A
instantaneous pick-up adjustment type Iifixed
long time pick-up adjustment range160...320 A
trip unit rating320-320 A at 65 °C
thermal memory20 minutes before and after tripping
[tr] long-time delay adjustment range10-10 s at 7.2 x Ir for trip class 10 120-120 s at 1.5 x Ir for trip class 5 20-20 s at 7.2 x Ir for trip class 20 240-240 s at 1.5 x Ir for trip class 10 26-26 s at 6 x Ir for trip class 20 480-480 s at 1.5 x Ir for trip class 20 5-5 s at 7.2 x Ir for trip class 5 13.5-13.5 s at 6 x Ir for trip class 10 6.5-6.5 s at 6 x Ir for trip class 5
short-time delay adjustment typefixed
[Isd] short-time pick-up adjustment range5...13 x Ir
short-time pick-up adjustment type Isdadjustable 9 settings
complementary motor protectionphase unbalance
motor tripping class20 5 10
Okolje
Temperatura okoliškega zraka za delovanje-35-70 °C
IP stopnja zaščiteIP40 conforming to IEC 60529
Temperatura okoliškega zraka za skladiščenje-55-85 °C
overvoltage categoryclass II
IK stopnja zaščiteIK07 conforming to IEC 62262
Certifikati izdelkovEAC Marine CCC
StandardiEN/IEC 60947 UL 508
electrical shock protection classclass II