Opis

trip unit Micrologic 2.3 M for Compact NSX 400/630 circuit breakers, electronic, rating 320 A, 3 poles 3d

Tehnične lastnosti

Glavno
Serija izdelkaNSX400...630
network typeAC
Izdelek ali sestavni delcontrol unit
product nameMicrologic
Skupina izdelkovCompact
Opis polov3P
Aplikacija napravemotor
trip unit technologyelectronic
network frequency50/60 Hz
trip unit nameMicrologic 2.3 M
trip unit rating320-320 A at 65 °C
protected poles description3t
protection typeL : for overload protection (long time) So : for short time short-circuit protection with fixed delay I : for instantaneous short-circuit protection
Združljivost serije/obsegaCompact NSX400 Compact NSX630
trip unit protection functionsLSoI
Komplementarno
mounting modefixed
[Ue] rated operational voltage690 V AC 50/60 Hz
long time pick-up adjustment type Iradjustable 9 settings
instantaneous pick-up adjustment range4800 A
long time delay adjustment typefixed
instantaneous pick-up adjustment type Iifixed
long time pick-up adjustment range160...320 A
thermal memory20 minutes before and after tripping
[tr] long-time delay adjustment range120-120 s at 1.5 x Ir for trip class 5 6.5-6.5 s at 6 x Ir for trip class 5 5-5 s at 7.2 x Ir for trip class 5 240-240 s at 1.5 x Ir for trip class 10 13.5-13.5 s at 6 x Ir for trip class 10 10-10 s at 7.2 x Ir for trip class 10 480-480 s at 1.5 x Ir for trip class 20 26-26 s at 6 x Ir for trip class 20 20-20 s at 7.2 x Ir for trip class 20
short-time delay adjustment typefixed
[tsd] short-time delay adjustment range0.01-0.01 s
[Isd] short-time pick-up adjustment range5...13 x Ir
short-time pick-up adjustment type Isdadjustable 9 settings
complementary motor protectionphase unbalance
motor tripping class10 20 5
Okolje
Temperatura okoliškega zraka za delovanje-25-70 °C
Temperatura okoliškega zraka za skladiščenje-50-85 °C
Certifikati izdelkovCCC Marine EAC
StandardiUL 508 EN/IEC 60947-2