Menu
Vaša košarica

LV430804 Schneider

LV430804  Schneider
LV430804 Schneider

Opis

circuit breaker Compact NSX160H, 70 kA at 415 VAC, Micrologic 5.2 A trip unit 160 A, 4 poles 4d

Tehnične lastnosti

Glavno
[In] rated current160 A at 40 °C
Serija izdelkaNSX100...250
network typeAC
breaking capacity codeH 70 kA 415 V AC
Izdelek ali sestavni delcircuit breaker
product nameCompact NSX
utilisation categorycategory A
Skupina izdelkovCompact
breaking capacity10 kA at 600 V AC 50/60 Hz conforming to UL 508 85 kA at 240 V AC 50/60 Hz conforming to UL 508 65 kA at 480 V AC 50/60 Hz conforming to UL 508 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
suitability for isolationyes conforming to EN 60947-2 yes conforming to IEC 60947-2
Opis polov4P
Aplikacija napravedistribution
Kratko ime napraveCompact NSX160H
trip unit technologyelectronic
network frequency50/60 Hz
[Ics] rated service breaking capacity10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 100 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 65 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 70 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
trip unit nameMicrologic 5.2 A
protected poles description3t + 1.6 N 3t + N/2 3t 4t
neutral positionleft
[Ue] rated operational voltage690 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage8 kV
[Ui] rated insulation voltage800 V AC 50/60 Hz
pollution degree3 conforming to IEC 60664-1
trip unit protection functionsLSI
Komplementarno
Višina161 mm
mounting supportbackplate
Teža izdelka2.6 kg
control typetoggle
mounting modefixed
electrical durability10000 cycles 440 V In/2 conforming to IEC 60947-2 15000 cycles 690 V In/2 conforming to IEC 60947-2 20000 cycles 440 V In conforming to IEC 60947-2 7500 cycles 690 V In conforming to IEC 60947-2
mechanical durability40000 cycles
Kompatibilnostna kodaNSX160
local signallingLED 105 % Ir LED 90 % Ir LED ready
Širina140 mm
Globina86 mm
long time pick-up adjustment type Iradjustable
upside connectionfront
downside connectionfront
protection typeL : for overload protection (long time) S : for short time short-circuit protection I : for instantaneous short-circuit protection
connection pitch35 mm
instantaneous pick-up adjustment range1.5...15 x In
long time delay adjustment typeadjustable
instantaneous pick-up adjustment type Iiadjustable
neutral protection setting0.5 x Ir (3t + N/2) 1 x Ir (4t) 1.6 x Ir (3t + OSN) no protection (3t)
long time pick-up adjustment range63...160 A
display typeLCD display
auxiliary contact compositionwithout
trip unit rating160-160 A at 40 °C
thermal memory20 minutes before and after tripping
[tr] long-time delay adjustment range15-400 s at 1.5 x Ir 0.35-11 s at 7.2 x Ir 0.5-16 s at 6 x Ir
type of measurementammeter
zone selective interlocking ZSIwith
short-time delay adjustment typeadjustable
[tsd] short-time delay adjustment range0-0.4 s
[Isd] short-time pick-up adjustment range1.5...10 x Ir
short-time pick-up adjustment type Isdadjustable
communication of datamaintenance indicators instantaneous and demand values demand current and power protection and alarm settings maximeters/minimeters time-stamped histories and event tables power quality energy metering
electrical data recordingmaintenance indicators
Okolje
Temperatura okoliškega zraka za delovanje-35-70 °C
IP stopnja zaščiteIP40 conforming to IEC 60529
Temperatura okoliškega zraka za skladiščenje-55-85 °C
overvoltage categoryclass II
IK stopnja zaščiteIK07 conforming to IEC 62262
Certifikati izdelkovMarine EAC CCC
StandardiEN/IEC 60947 UL 508
electrical shock protection classclass II