Opis

trip unit TM16D for Compact NSX 100 circuit breakers, thermal magnetic, rating 16 A, 4 poles 4d

Tehnične lastnosti

Glavno
Serija izdelkaNSX100...250 DC NSX100...250
network typeAC DC
Izdelek ali sestavni deltrip unit
Skupina izdelkovCompact
Opis polov4P
Aplikacija napravedistribution
trip unit technologythermal-magnetic
network frequency50/60 Hz
trip unit nameTM-D
trip unit rating16-16 A at 40 °C
protected poles description4t
protection typeL : for overload protection (thermal) I : for short-circuit protection (magnetic)
neutral positionleft
Združljivost serije/obsegaCompact NSX100 Compact NSX100 DC
trip unit protection functionsLI
Komplementarno
mounting modefixed
[Ue] rated operational voltage690 V AC 50/60 Hz 750 V DC
long time pick-up adjustment type Iradjustable
long time delay adjustment typefixed
neutral protection setting1 x Ir (4t)
long time pick-up adjustment range0.7...1 x In
[tr] long-time delay adjustment range120-400 s at 1.5 x In 15-15 s at 6 x Ir
short-time delay adjustment typefixed
[Isd] short-time pick-up adjustment range190 A
short-time pick-up adjustment type Isdfixed
Okolje
Temperatura okoliškega zraka za delovanje-25-70 °C
Temperatura okoliškega zraka za skladiščenje-50-85 °C
Certifikati izdelkovMarine CCC EAC
StandardiEN/IEC 60947-2 UL 508