Menu
Vaša košarica

33344 Schneider Electric

33344  Schneider Electric
33344 Schneider Electric

Opis

circuit breaker basic frame, Compact NS 1000N, 50kA at 415VAC, 1000A, drawout, manually operated, without trip unit, 4P

Tehnične lastnosti

Glavno
Serija izdelkaNS630b...1600
network typeAC
breaking capacity codeN
Izdelek ali sestavni delbasic frame
product nameCompact NS
utilisation categorycategory B
Skupina izdelkovCompact
suitability for isolationyes conforming to IEC 60947-2
Opis polov4P
Aplikacija napravedistribution
Kratko ime napraveCompact NS1000N
circuit breaker nameCompact NS1000N
neutral positionleft
Komplementarno
network frequency50/60 Hz
[Ics] rated service breaking capacity30 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 (manual operation) 40 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 (manual operation) 50 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 (manual operation) 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 (manual operation) 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 (manual operation)
Višina327 mm
mounting supportbackplate
control typetoggle rotary handle
[Ui] Nazivna izolacijska trdnost800 V AC 50/60 Hz conforming to IEC 60947-2
mounting modedrawout
electrical durability2000 cycles 690 V AC 50/60 Hz In conforming to IEC 60947-2 4000 cycles 690 V AC 50/60 Hz In/2 conforming to IEC 60947-2 5000 cycles 440 V AC 50/60 Hz In conforming to IEC 60947-2 6000 cycles 440 V AC 50/60 Hz In/2 conforming to IEC 60947-2
mechanical durability10000 cycles conforming to IEC 60947-2
Kompatibilnostna kodaNS1000
[Uimp] rated impulse withstand voltage8 kV conforming to IEC 60947-2
Širina280 mm
Globina147 mm
[Ue] rated operational voltage690 V AC 50/60 Hz conforming to IEC 60947-2
[In] rated current1000 A at 50 °C
protection typewithout protection
breaking capacity30 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2
[Icw] rated short-time withstand current19.2 kA 1 s conforming to IEC 60947-2
connection pitch70 mm
integral instant protection40-40 kA
circuit breaker CT rating1000 A
Okolje
Temperatura okoliškega zraka za delovanje-25-70 °C
IP stopnja zaščiteIP40 conforming to IEC 60529
Stopnja onesnaženosti3 conforming to IEC 60947
Temperatura okoliškega zraka za skladiščenje-50-85 °C
IK stopnja zaščiteIK07 conforming to EN 50102
Certifikati izdelkovASEFA ASTA LCIE
StandardiIEC 60947-2
power losses50 W